AIR CONDITIONING - Rafstjorn
AIR CONDITIONING - Rafstjorn
AIR CONDITIONING - Rafstjorn
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
14. Start-up<br />
Supply voltage to the cooling unit.<br />
If the temperature in the room is lower than the temperature set on the thermostat the<br />
evaporator fan will start and will cause air recirculation in the cabinet.<br />
If the temperature in the room is higher than the temperature set on the thermostat then the<br />
compressor and the condenser fan will start. They will operate until the temperature in the<br />
room falls below the value set on the thermostat.<br />
Note!<br />
Avoid sudden stops and re-starts. At least 3 minutes should elapse between a stop and the<br />
next re-start.<br />
15. Adjusting the Temperature<br />
Note!<br />
Excessively low cabinet temperatures may cause serious problems to the cabinet parts<br />
and require an increased power consumption for a higher cooling capacity.<br />
Mechanical Thermostat<br />
Adjustment<br />
The adjustment should be made by experienced<br />
personnel by acting on the thermostat pin with a<br />
screwdriver after having switched off the voltage<br />
and having removed the unit's front panel.<br />
The thermostat has a 4°C hysteresis, therefore<br />
the compressor will start at a temperature, which<br />
is 4 Kelvin above the stop point. After the<br />
adjustment replace the front panel and re-supply<br />
voltage.<br />
Adjustment screw<br />
E/0304/31A/29