<strong>EY</strong>-<strong>RC416</strong><br />
Parameterisation of the intelligent unitary <strong>controller</strong>s<br />
Network variables<br />
The <strong>controller</strong> software supports structured SNVTs and UNVTs of 1<br />
and 2 bytes in length. 16 NVIs and 20 NVOs (with changeable<br />
types and lengths) are available.<br />
User programme<br />
Simple configuration of all device parameters, including inputs,<br />
outputs and setpoints for heating and cooling. It is also possible to<br />
parameterise additional integrated functions such as <strong>volume</strong> <strong>flow</strong><br />
calibration, CO2-led <strong>volume</strong> <strong>flow</strong> control, limit value alarms, load<br />
shedding, frost protection and slave operating mode.<br />
Support for EnOcean ® radio transmitters.<br />
The <strong>EY</strong>-<strong>RC416</strong>F002 intelligent unitary <strong>controller</strong> has an integrated<br />
EnOcean ® radio receiver. This ensures excellent compatibility with<br />
many wireless sensors and peripheral devices that are equipped<br />
with EnOcean ® technology.<br />
Receiver module:<br />
Reception range:<br />
EnOcean ® RCM120, 868.3 MHz<br />
10-30 m in buildings, approx. 300 m<br />
outdoors<br />
The EnOcean ® reception module allows the use of up to 5 wireless<br />
sensors for room temperature, channel temperature or humidity.<br />
Window and door contacts as well as light switches are supported<br />
with up to 4 channels.<br />
Functional profile<br />
nviRequest<br />
SNVT_obj_request<br />
<strong>ecos416</strong> Node<br />
Object Type #0<br />
Mandatory<br />
Network<br />
Variables<br />
Optional<br />
Network<br />
Variables<br />
Configuration Properties<br />
Device Major Version (optional)<br />
Device Minor Version (optional)<br />
Location (optional)<br />
Maximum Send Time (optional)<br />
Manufacturer<br />
Network<br />
Variables<br />
Manufacturer Configuration Properties<br />
Hardware Information<br />
nvoStatus<br />
SNVT_obj_status<br />
nvoFileDirectory<br />
SNVT_address<br />
nvoVAVstate<br />
SNVT_state_64<br />
nvoVAValarm<br />
SNVT_state_64<br />
nviSpaceTemp<br />
SNVT_temp_p<br />
nviAirFlow<br />
SNVT_<strong>flow</strong><br />
nviApplicMode<br />
SNVT_hvac_mode<br />
nviCO2<br />
SNVT_ppm<br />
nviEmergOverride<br />
SNVT_hvac_emerg<br />
nviFlowOverride<br />
SNVT_hvac_overid<br />
nviOccManCmd<br />
SNVT_occupancy<br />
<strong>ecos416</strong> VAV<br />
Object Type #8502<br />
Mandatory<br />
Network<br />
Variables<br />
Optional<br />
Network<br />
Variables<br />
nvoSpaceTemp<br />
SNVT_temp_p<br />
nvoUnitStatus<br />
SNVT_hvac_status<br />
nvoAirFlow<br />
SNVT_<strong>flow</strong><br />
nvoEffectOccup<br />
SNVT_occupancy<br />
nvoEffectSetpt<br />
SNVT_temp_p<br />
nvoFlowSetpoint<br />
SNVT_<strong>flow</strong><br />
nvoTerminalLoad<br />
SNVT_lev_percent<br />
nviHwOutputx (x=1-6)<br />
SNVT_switch<br />
<strong>ecos416</strong> Hardware Input<br />
Object Type #1<br />
Mandatory<br />
Network<br />
Variables<br />
Configuration Properties<br />
Maximum Range (optional)<br />
Minimum Range (optional)<br />
Minimum Send Delta (optional)<br />
Maximum Send Time (optional)<br />
Minimum Send Time (optional)<br />
Override Value (optional)<br />
Manufacturer Configuration Properties<br />
Default Value<br />
Hardware Properties<br />
Input Signal Conditioning<br />
Object Major Version<br />
Object Minor Version<br />
Offset<br />
Translation Table<br />
<strong>ecos416</strong> Hardware Output<br />
Object Type #1<br />
Mandatory<br />
Network<br />
Variables<br />
Configuration Properties<br />
Maximum Receive Time (optional)<br />
Override Value (optional)<br />
Manufacturer Configuration Properties<br />
Default Value<br />
Hardware Properties<br />
Maximum Range<br />
Minimum Range<br />
Object Major Version<br />
Object Minor Version<br />
Output Signal Conditioning<br />
PWM Period<br />
nvoHwInputx (x=1-4)<br />
SNVT_temp_f<br />
(changeable)<br />
nviOutdoorTemp<br />
SNVT_temp_p<br />
nviSetPoint<br />
SNVT_temp_p<br />
nviSetptOffset<br />
SNVT_temp_p<br />
nviWaterTemp<br />
SNVT_temp_p<br />
nviCalibCode<br />
SNVT_str_16<br />
nviDuctInTemp<br />
SNVT_temp_p<br />
nviFlowCalib<br />
UNVT_<strong>flow</strong>_calib<br />
nviHotAir<br />
SNVT_switch<br />
nviHotWater<br />
SNVT_switch<br />
nviOccCmd<br />
SNVT_occupancy<br />
nviShedding<br />
SNVT_switch<br />
nviSlave<br />
SNVT_lev_percent<br />
nviVAVinfo<br />
SNVT_str_asc<br />
(changeable)<br />
Configuration Properties<br />
Temperature Set Points (mandatory)<br />
ECC-VAV Send Heartbeat SCC-VAV (mandatory) Controller<br />
Bypass Time (optional)<br />
Object Type #8502<br />
Duct Area (optional)<br />
Maximum Flow (optional)<br />
Minimum Flow (optional)<br />
Minimum Flow for Heating (optional)<br />
Minimum Send Time (optional)<br />
Nominal Flow (optional)<br />
Receive Heartbeat (optional)<br />
Space CO Limit (optional)<br />
2<br />
Manufacturer<br />
Network<br />
Variables<br />
nvoComInputs<br />
UNVT_gen_values<br />
nvoCtrlOut1<br />
SNVT_switch<br />
.<br />
.<br />
.<br />
nvoCtrlOut6<br />
SNVT_switch<br />
nvoCtrlStatus<br />
UNVT_8_ctrl_status<br />
nvoDamperPos<br />
SNVT_lev_percent<br />
nvoOccState<br />
SNVT_occupancy<br />
nvoRoomInfo<br />
UNVT_2room_info<br />
nvoVAVinfo<br />
SNVT_str_asc<br />
Manufacturer Configuration Properties<br />
Please refer to the list of UCPTs in the User Guide<br />
The Manufacturer CPs are configurable using the<br />
device plug-in<br />
4/5 www.sauter-controls.com