UNCLASSIFIED<br />

OPERATIONAL PROCEDURE - <strong>Elster</strong> <strong>LCR</strong>-<strong>212</strong> <strong>Single</strong> <strong>Phase</strong><br />

<strong>Load</strong> <strong>Control</strong> Ripple Receiver Installation and<br />

Use<br />

CEOP8086<br />

8 Zellweger DECABIT<br />

9 L & G S 52<br />

10 L & G S 56<br />

11 ZPA<br />

• the secure VERSACOM protocol<br />

7 RECEIVER STATUS<br />

The following receiver status information is stored in the microcontroller's EEPROM and RAM<br />

and, using a special adaptor, can be read out through the serial interface by a PC or<br />

handheld unit.<br />

• Number of switching actions executed<br />

The number of switching actions executed is counted separately for each relay and is stored<br />

in the RAM.<br />

• Number of test transmissions<br />

Specific test commands can be defined for testing purposes. The number of commands<br />

received is stored in the RAM.<br />

• Last telegram received<br />

The pulse pattern of the last telegram received is stored in the RAM.<br />

• Signal level of the AF voltage<br />

The signal level of the AF voltage of the last received telegram is measured with an<br />

accuracy of +/- 10 % and is stored in the RAM.<br />

• Signal absence sensing<br />

The number of detected transmitter failures is counted and stored in the RAM.<br />

All status information is stored in the microcontroller's internal RAM and is cleared in the<br />

event of a power failure.<br />

8 MECHANICAL DESIGN<br />

The <strong>LCR</strong><strong>212</strong> ripple control receiver can be used for mounting on a meter board or with the<br />

optional meter mounting adaptor, on a meter terminal cover.<br />

The electronic circuitry is mounted on an PCB. The board is covered by a PCB holder, thus<br />

providing shock hazard protection even when the cover of the receiver is open.<br />

The receiver can be equipped with up to 3 relays, counted 1-2-3 from left to right.<br />

The bistable 40A output relays are of the plug-in type. 2 connection terminals for wires up<br />

to a diameter of 10 mm² are available for each relay.<br />

9 PROGRAMMING AND TEST EQUIPMENT<br />

To program the receiver, its RS 232 serial interface is connected either via an optical probe<br />

or an electrical adaptor to a PC or a hand-held programmer LCP.<br />

All receiver parameters such as the frequency, ripple control system and other user-defined<br />

data are transferred to the microcontroller's EEPROM in this way.<br />

22 March 2011 - Issue 3<br />

Approved By: General Manager Technical Services<br />

Page 13 of 17<br />

UNCLASSIFIED<br />

UNCONTROLLED COPY IF PRINTED