Flow rate setting<br />
Each <strong>LVC</strong>-<strong>LowVelocity</strong> carries a sticker with a flow rate scale to<br />
determine the setting values at the customer’s site (see example<br />
above, nominal size 200).<br />
Variable flow rate control<br />
The required flow rates must be set by the customer. If Vmin is<br />
set higher than V max , Vmin is provided as a constant flow rate<br />
even if a control signal is transmitted.<br />
If Vmin is set to 0%, control is between shut-off and V max . If the<br />
control signal falls below 0.1 VDC, the control damper closes<br />
(leakage flow only).<br />
Vmin<br />
V max<br />
Constant flow rate control<br />
The constant flow rate is set with the Vmin potentiometer. Any<br />
setting on the V max potentiometer is in this case irrelevant.<br />
Vmin<br />
V max<br />
BMS operation<br />
To have the BMS determine the volume flow rate, the Vmin<br />
potentiometer must be set to 0% and the V max potentiometer<br />
to 100%. If the control signal falls below 0.1 VDC, the control<br />
damper closes (leakage flow only).<br />
Vmin<br />
V max<br />
Factory setting<br />
Units are delivered with settings Vmin = 40 % and<br />
V max = 80%.<br />
Vmin<br />
V max<br />
10