Flow rate setting<br />

Each <strong>LVC</strong>-<strong>LowVelocity</strong> carries a sticker with a flow rate scale to<br />

determine the setting values at the customer’s site (see example<br />

above, nominal size 200).<br />

Variable flow rate control<br />

The required flow rates must be set by the customer. If Vmin is<br />

set higher than V max , Vmin is provided as a constant flow rate<br />

even if a control signal is transmitted.<br />

If Vmin is set to 0%, control is between shut-off and V max . If the<br />

control signal falls below 0.1 VDC, the control damper closes<br />

(leakage flow only).<br />

Vmin<br />

V max<br />

Constant flow rate control<br />

The constant flow rate is set with the Vmin potentiometer. Any<br />

setting on the V max potentiometer is in this case irrelevant.<br />

Vmin<br />

V max<br />

BMS operation<br />

To have the BMS determine the volume flow rate, the Vmin<br />

potentiometer must be set to 0% and the V max potentiometer<br />

to 100%. If the control signal falls below 0.1 VDC, the control<br />

damper closes (leakage flow only).<br />

Vmin<br />

V max<br />

Factory setting<br />

Units are delivered with settings Vmin = 40 % and<br />

V max = 80%.<br />

Vmin<br />

V max<br />

10