Acoustic quick selection<br />

Using quick selection for sizing <strong>VAV</strong> controllers will rapidly<br />

provide optimum results. The first selection criteria are the given<br />

volume flow rates Vmin and V max . The expected sound pressure<br />

level in the room is then determined from the static pressure<br />

differential. The quick selection tables are based on normally<br />

accepted attenuation levels; if the sound pressure level exceeds<br />

the required level, a larger volume flow controller and/or a<br />

silencer is required.<br />

For dimensions and technical data for type CS sound<br />

attenuators refer to leaflet 6/5/EN/....<br />

For a more detailed selection and design of<br />

type <strong>LVC</strong>-<strong>LowVelocity</strong> <strong>VAV</strong> controllers refer to the<br />

Easy Product Finder design programme on our homepage.<br />

System attenuation in dB/oct. acc. to VDI 2081<br />

(values incorporated in the quick selection table)<br />

fm in Hz<br />

63<br />

Duct bend 0 0 1 2 3 3 3 3<br />

Room attenuation 5 5 5 5 5 5 5 5<br />

End reflection 10 5 2 0 0 0 0 0<br />

125<br />

250<br />

500<br />

Correction for distribution into the duct system<br />

(values incorporated in the quick selection table)<br />

V<br />

1000<br />

2000<br />

4000<br />

l/s 150 200 250 300<br />

m³/h 540 720 900 1080<br />

dB per octave 0 1 2 3<br />

8000<br />

4 dB/octave ceiling reduction and 5 dB/octave room attenuation<br />

have been allowed for in the calculation of case-radiated noise.<br />

Quick selection of sound pressure level LPA in dB(A)<br />

Air-regenerated noise<br />

Case-radiated<br />

noise<br />

Nominal<br />

size<br />

V<br />

∆pst<br />

min<br />

∆V<br />

∆pst in Pa ∆pst in Pa ∆pst in Pa ∆pst ∆pst in Pa<br />

50 150 300 50 150 300 50 150 300 300 50 150 300<br />

Without CS<br />

CS050<br />

L = 500<br />

CS050<br />

L = 1000<br />

CS050<br />

L = 1500<br />

LPA LPA₁ LPA₁ LPA₁ LPA₂<br />

l/s m³/h Pa ±% dB(A) dB(A) dB(A) dB(A) dB(A)<br />

8 30 30 15 27 37 43 14 22 28 4 10 15 10 9 21 30<br />

125<br />

30 110 30 12 35 45 51 24 33 39 17 24 29 26 16 27 34<br />

55 200 30 8 39 49 55 30 39 44 24 31 36 33 20 30 38<br />

75 270 30 5 42 52 58 34 42 48 29 36 41 38 22 33 40<br />

12 45 30 15 28 38 45 19 28 34 12 19 24 20 8 20 28<br />

160<br />

50 180 30 12 34 44 51 25 34 40 19 27 32 28 17 28 36<br />

85 305 30 8 36 46 54 29 37 43 23 31 36 33 21 32 39<br />

120 430 30 5 38 48 56 21 39 45 28 34 39 36 23 34 42<br />

20 70 30 15 31 40 47 21 30 36 13 20 26 23 10 21 29<br />

200<br />

75 270 30 12 35 45 52 25 34 42 19 26 32 29 17 29 37<br />

135 485 30 8 36 47 54 28 37 44 22 29 35 33 21 32 40<br />

190 685 30 5 36 47 55 29 37 45 26 31 36 35 23 34 42<br />

30 110 30 15 31 41 48 24 32 40 17 25 32 30 16 27 34<br />

250<br />

120 430 30 12 36 47 54 28 38 46 21 30 38 35 24 35 42<br />

210 755 30 8 36 47 55 28 39 47 23 31 39 36 27 38 46<br />

300 1080 30 5 36 48 55 29 39 48 25 32 39 37 29 40 48<br />

7