FLAT SMOOTH & SLOPED CEILINGS<br />

RESIDENTIAL SPRINKLERS<br />

Horizontal Sidewall,<br />

Recessed Horizontal<br />

Sidewall<br />

Pressure (PSI)<br />

Central, Gem <strong>and</strong> Star Viking Reliable Victaulic Globe Automatic<br />

5.5 4.3 4.3<br />

4.2 TY1334 VK442 VK440 VK448 4.0 - F1 RES40 4.2 4.2 4.2<br />

8/12 8/12 8/12 8/12 8/12 8/12<br />

Flat 4/12 Slope 8/12 Slope Flat Slope Flat Slope Flat Slope Flat 8/12 Slope Flat Slope Flat Slope Flat Slope<br />

Room Size Rating At Across At Across At At At Across At<br />

(ft. x ft.) (F) Peak Slope Peak Slope Peak Peak Peak Slope Peak<br />

12 X 12 155 8.2 8.2 14.5 8.2 14.5* na 14.6 na 19.5 na na 10.6 10.6 18.1 9.6 9.6 9.6 na 23.0 na 4-6<br />

12 X 12 155 9.6 9.6 18.4 9.6 na 14.6 na 19.5 na na na 10.6 10.6 na na na na na na na 6-12<br />

12 X 12 175 8.2 8.2 14.5 8.2 14.5* na 14.6 na 19.5 na na 10.6 10.6 na na na 9.6 na na na 4-6<br />

12 X 12 175 9.6 9.6 18.4 9.6 na 14.6 na 19.5 na na na 10.6 10.6 na na na na na na na 6-12<br />

Deflector<br />

to ceiling<br />

(in.)<br />

14 X 14 155 11.1 11.1 14.5 11.1 14.5* na 16.0 na na na na 16.0 16.0 18.1 14.5 22.7 12.8 na 23.0 na 4-6<br />

14 X 14 155 16.4 16.4 18.4 16.4 na 16.0 na 23.9 na na na 18.1 18.1 na na na na na na na 6-12<br />

14 X 14 175 14.5 11.1 14.5 11.1 14.5* na 16.0 na na na na 16.0 16.0 na na na 12.8 na na na 4-6<br />

14 X 14 175 18.4 16.4 18.4 16.4 na 16.0 na 23.9 na na na 18.1 18.1 na na na na na na na 6-12<br />

16 X 16 155 14.5 14.5 14.5 14.5 14.5* na 19.0 na na na na 18.1 18.1 18.1 22.7 na 14.5 na 35.0 na 4-6<br />

16 X 16 155 18.4 18.4 18.4 18.4 na 19.0 na na na na na 25.0 25.0 na na na na na na na 6-12<br />

16 X 16 175 14.5 14.5 14.5 14.5 14.5* na 19.0 na na na na 20.2 18.1 na na na 14.5 na na na 4-6<br />

16 X 16 175 18.4 18.4 18.4 18.4 na 19.0 na na na na na 25.0 25.0 na na na na na na na 6-12<br />

16 X 18 155 20.5 20.5 27.4 20.5 na na 25.9 na na 28.6 na 25.0 25.0 na 30.0 na 20.5 na na na 4-6<br />

16 X 18 155 25.0 25.0 27.4 25.0 na 24.1 na na na 31.2 na na na na na na na na na na 6-12<br />

16 X 18 175 20.5 20.5 27.4 20.5 na na 25.9 na na 28.6 na 25.0 27.6 na na na 20.5 na na na 4-6<br />

16 X 18 175 25.0 25.0 27.4 25.0 na 24.1 na na na 31.2 na na na na na na na na na na 6-12<br />

18 X 18 155,175 na na na na na na na na na na na 30.2 na na na na na na na na 4-6<br />

16 X 20 155 30.0 32.7 30.0* 32.7 na na na na na 33.8 na 33.1 33.1 na 30.0 na 30.0 na na na 4-6<br />

16 X 20 155 38.3 38.3 38.3* 38.3 na na na na na 36.6 na na na na na na na na na na 6-12<br />

16 X 20 175 30.0 32.7 30.0* 32.7 na na na na na 33.8 na 33.1 33.1 na na na 30.0 na na na 4-6<br />

16 X 20 175 38.3 38.3 38.3* 38.3 na na na na na 36.6 na na na na na na na na na na 6-12<br />

* = 3 head design across slope<br />

Figure 5 - Pressures for Horizontal Sidewalls <strong>and</strong> Recessed Horizontal Sidewalls<br />