.03 Post-fire Safe Shutdown Circuit Analysis<br />
a. Inspection Scope<br />
6<br />
On a sample basis, the inspectors evaluated the adequacy of separation provided for<br />
electrical cables of safe shutdown systems. The inspectors also reviewed relevant<br />
portions of three Fire Event Safe Shutdown Evaluations, which contained the licensee’s<br />
safe shutdown analysis for the selected fire areas. The reports reviewed are listed in<br />
the attachment. The analysis intended to show that fire damage to <strong>com</strong>ponents and<br />
cables located within the chosen fire areas would not prevent safe shutdown. The<br />
inspectors then focused on any cases of redundant shutdown circuits routed in the<br />
same fire area.<br />
The inspectors made a detailed review of selected control circuits as listed in the<br />
attachment. Cables that could interfere with safe shutdown if they were routed in the<br />
selected fire areas were identified. The inspectors then evaluated the routing of these<br />
cables by reviewing the <strong>com</strong>puterized cable schedule which indicated the specific<br />
raceways through which the cables were routed together with the fire zone information.<br />
The inspectors pin-pointed the location of raceways in the field as necessary to<br />
determine if they could be in the zone of influence of fire emanating from transient<br />
<strong>com</strong>bustibles or in-situ fire sources.<br />
The inspectors also reviewed a sample of electrical coordination studies to verify that<br />
fire induced faults in load cables emanating from required sources of electric power<br />
would not cause a loss of power and prevent safe shutdown. Selective coordination for<br />
ground faults on the 4160 V system was checked for the following relays: 151NRB<br />
(transformer 1XNRB neutral), 151G (at in<strong>com</strong>ing breaker to bus 1BA03) and 150/151GF<br />
(at feeder breaker to load center 1NB10). The inspectors examined the installed relay<br />
setpoints as well as the last <strong>com</strong>pleted calibration records to verify that the relays were<br />
installed in accordance with design documents.<br />
b. Findings<br />
No findings of significance were identified.<br />
.04 Alternative Shutdown Capability and Operational Implementation of Alternative<br />
Shutdown<br />
a. Inspection Scope<br />
Alternative shutdown capability and operational implementation of alternative shutdown<br />
from outside the main control room was not examined during this inspection. This is<br />
because the selected fire zones (i.e., 38, 42B, and 73) are train B shutdown areas using<br />
the controls in the main control room, for the most part, with limited local manual<br />
actions. Manual operations using the train B remote shutdown panel were reviewed as<br />
related to fire response for FZ 38. The ability to perform the local manual actions, the<br />
access and egress routes for the operators, emergency lighting, and environmental<br />
conditions at the remote locations was examined by the team and discussed in other<br />
sections of the report.