.03 Post-fire Safe Shutdown Circuit Analysis<br />

a. Inspection Scope<br />

6<br />

On a sample basis, the inspectors evaluated the adequacy of separation provided for<br />

electrical cables of safe shutdown systems. The inspectors also reviewed relevant<br />

portions of three Fire Event Safe Shutdown Evaluations, which contained the licensee’s<br />

safe shutdown analysis for the selected fire areas. The reports reviewed are listed in<br />

the attachment. The analysis intended to show that fire damage to <strong>com</strong>ponents and<br />

cables located within the chosen fire areas would not prevent safe shutdown. The<br />

inspectors then focused on any cases of redundant shutdown circuits routed in the<br />

same fire area.<br />

The inspectors made a detailed review of selected control circuits as listed in the<br />

attachment. Cables that could interfere with safe shutdown if they were routed in the<br />

selected fire areas were identified. The inspectors then evaluated the routing of these<br />

cables by reviewing the <strong>com</strong>puterized cable schedule which indicated the specific<br />

raceways through which the cables were routed together with the fire zone information.<br />

The inspectors pin-pointed the location of raceways in the field as necessary to<br />

determine if they could be in the zone of influence of fire emanating from transient<br />

<strong>com</strong>bustibles or in-situ fire sources.<br />

The inspectors also reviewed a sample of electrical coordination studies to verify that<br />

fire induced faults in load cables emanating from required sources of electric power<br />

would not cause a loss of power and prevent safe shutdown. Selective coordination for<br />

ground faults on the 4160 V system was checked for the following relays: 151NRB<br />

(transformer 1XNRB neutral), 151G (at in<strong>com</strong>ing breaker to bus 1BA03) and 150/151GF<br />

(at feeder breaker to load center 1NB10). The inspectors examined the installed relay<br />

setpoints as well as the last <strong>com</strong>pleted calibration records to verify that the relays were<br />

installed in accordance with design documents.<br />

b. Findings<br />

No findings of significance were identified.<br />

.04 Alternative Shutdown Capability and Operational Implementation of Alternative<br />

Shutdown<br />

a. Inspection Scope<br />

Alternative shutdown capability and operational implementation of alternative shutdown<br />

from outside the main control room was not examined during this inspection. This is<br />

because the selected fire zones (i.e., 38, 42B, and 73) are train B shutdown areas using<br />

the controls in the main control room, for the most part, with limited local manual<br />

actions. Manual operations using the train B remote shutdown panel were reviewed as<br />

related to fire response for FZ 38. The ability to perform the local manual actions, the<br />

access and egress routes for the operators, emergency lighting, and environmental<br />

conditions at the remote locations was examined by the team and discussed in other<br />

sections of the report.