University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5496 <strong>PE</strong> Utilities Building in Riverside, CA<br />

900 University Avenue<br />

7. Urinals - Men’s Restroom at <strong>PE</strong> Utilities Building.<br />

Memo:<br />

Areas noted in compliance:<br />

A clear floor space that is a minimum 30” wide by 48” deep is provided in front of the urinal to allow forward approach.<br />

44” maximum height to flush valve above finished floor.<br />

5 lb max. pressure to operate valve.<br />

Walls within 24” of front and sides of urinals are smooth, hard and non-absorbent to 48” height, and are not adversely<br />

affected by moisture.<br />

Areas not meeting new construction standards:<br />

17” maximum urinal rim height above the finished floor. (21”.)<br />

14” minimum projection and 17” maximum projection from the wall. (20-1/2”.)<br />

Recommendation:<br />

Replace/Install urinal.<br />

Photo #UCR P5496 <strong>PE</strong> Utilities Building-7-1 (originally 10)<br />