mMOTOR TECHNICAL MANUAL<br />

Voltage.<br />

This should be set to the line voltage of the supply. It is necessary for power calculations<br />

and is used for the Under / Overvoltage, Undervoltage Restart and Undervoltage<br />

Lockout protection features.<br />

As an example if the voltage input was connected between two phases on a 415V<br />

system this setting would be 415V. If however the voltage input was connected between<br />

a phase and neutral then this setting should be 240V.<br />

Voltage Ref.<br />

This parameter can be set to Ph-N (Phase to Neutral) or Ph-Ph (Phase to Phase) with a<br />

reverse feature to avoid re-wiring for phase correction to match the connection type<br />

above.<br />

E/F Primary.<br />

This setting allows the user to program the primary current rating of the protection class<br />

current transformer used to measure the earth fault current.<br />

If a residual current transformer connection is used to detect earth fault then the same<br />

setting as for CT Primary should be used.<br />

If the Internal Residual Connection is used for earth fault protection then this setting is<br />

hidden.<br />

KW Sample Period.<br />

This setting range 5 to 60 min in steps of 1min determines the period over which a<br />

measurement is taken to integrate the Kilowatt Hours value.<br />

P&B Engineering Issue 6 25/04/2005 Page 33