mMOTOR TECHNICAL MANUAL<br />
Voltage.<br />
This should be set to the line voltage of the supply. It is necessary for power calculations<br />
and is used for the Under / Overvoltage, Undervoltage Restart and Undervoltage<br />
Lockout protection features.<br />
As an example if the voltage input was connected between two phases on a 415V<br />
system this setting would be 415V. If however the voltage input was connected between<br />
a phase and neutral then this setting should be 240V.<br />
Voltage Ref.<br />
This parameter can be set to Ph-N (Phase to Neutral) or Ph-Ph (Phase to Phase) with a<br />
reverse feature to avoid re-wiring for phase correction to match the connection type<br />
above.<br />
E/F Primary.<br />
This setting allows the user to program the primary current rating of the protection class<br />
current transformer used to measure the earth fault current.<br />
If a residual current transformer connection is used to detect earth fault then the same<br />
setting as for CT Primary should be used.<br />
If the Internal Residual Connection is used for earth fault protection then this setting is<br />
hidden.<br />
KW Sample Period.<br />
This setting range 5 to 60 min in steps of 1min determines the period over which a<br />
measurement is taken to integrate the Kilowatt Hours value.<br />
P&B Engineering Issue 6 25/04/2005 Page 33