18.11.2014 Views

ESW Thermal Performance - Evapco

ESW Thermal Performance - Evapco

ESW Thermal Performance - Evapco

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Supplement to Bulletin 240C<br />

<strong>Thermal</strong> <strong>Performance</strong><br />

<strong>ESW</strong> Models 216-46K to 216-46N<br />

†<br />

<strong>Thermal</strong> performance certified by the Cooling Technology<br />

Institute (CTI) in accordance with CTI Standard STD-201<br />

COOLER CAPABILITY IN USGPM AT THE FOLLOWING TEMPERATURE CONDITIONS (°F)<br />

EWT 90° 90° 90° 95° 95° 95° 95° 95° 95° 100°<br />

LWT 80° 80° 80° 80° 80° 80° 85° 85° 85° 85°<br />

Model No. WB 68° 70° 72° 66° 68° 70° 75° 76° 78° 72°<br />

<strong>ESW</strong> 216-46K 1263 1128 976 1080 983 882 1216 1142 991 1109<br />

<strong>ESW</strong> 216-46L 1313 1173 1013 1123 1022 918 1257 1183 1028 1149<br />

<strong>ESW</strong> 216-46M * 1212 1052 1164 1061 956 1298 1216 1063 1183<br />

<strong>ESW</strong> 216-46N * 1271 1099 1231 1123 1007 1350 1272 1099 1239<br />

COOLER CAPABILITY IN USGPM AT THE FOLLOWING TEMPERATURE CONDITIONS (°F)<br />

EWT 100° 100° 97° 115° 115° 100° 102° 105° 105° 105°<br />

LWT 85° 85° 87° 90° 90° 90° 90° 90° 90° 90°<br />

Model No. WB 74° 76° 78° 74° 76° 80° 78° 76° 78° 80°<br />

<strong>ESW</strong> 216-46K 1005 898 1186 982 920 1305 1297 1238 1138 1026<br />

<strong>ESW</strong> 216-46L 1040 930 1221 1017 956 1343 1333 1273 1171 1059<br />

<strong>ESW</strong> 216-46M 1074 964 1257 1048 985 * * 1308 1207 1089<br />

<strong>ESW</strong> 216-46N 1128 1010 1309 1097 1027 * * * 1255 1143<br />

Notes:<br />

1. Conditions are based on WATER as the Cooling Fluid.<br />

2. CTI Certified performance capability based on Standard and Super Low Sound Fan.<br />

3. For more CTI Certified selections, consult EVAPCO’s iES Selection Program.<br />

4. High flow header connections may be required for some flow rates.<br />

* Flow outside limits allowed for model.<br />

† Mark owned by the Cooling Technology Institute.<br />

11

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!