Supplement to Bulletin 240C<br />

<strong>Thermal</strong> <strong>Performance</strong><br />

<strong>ESW</strong> Models 144-23I to 144-34L<br />

†<br />

<strong>Thermal</strong> performance certified by the Cooling Technology<br />

Institute (CTI) in accordance with CTI Standard STD-201<br />

COOLER CAPABILITY IN USGPM AT THE FOLLOWING TEMPERATURE CONDITIONS (°F)<br />

EWT 90° 90° 90° 95° 95° 95° 95° 95° 95° 100°<br />

LWT 80° 80° 80° 80° 80° 80° 85° 85° 85° 85°<br />

Model No. WB 68° 70° 72° 66° 68° 70° 75° 76° 78° 72°<br />

<strong>ESW</strong> 144-23I 536 472 400 439 392 347 516 482 407 454<br />

<strong>ESW</strong> 144-23J 577 511 431 471 422 374 553 515 436 485<br />

<strong>ESW</strong> 144-23K 607 535 452 494 446 394 578 538 455 507<br />

<strong>ESW</strong> 144-24I 594 522 446 486 439 385 575 536 455 506<br />

<strong>ESW</strong> 144-24J 642 565 484 528 475 419 619 577 494 546<br />

<strong>ESW</strong> 144-24K 680 598 513 557 501 444 650 606 519 574<br />

<strong>ESW</strong> 144-25I 639 560 481 524 475 417 623 580 493 549<br />

<strong>ESW</strong> 144-25J 695 609 524 572 515 457 676 626 535 594<br />

<strong>ESW</strong> 144-25K 733 646 554 607 546 484 709 660 565 628<br />

<strong>ESW</strong> 144-26I 678 592 507 555 500 442 662 615 523 583<br />

<strong>ESW</strong> 144-26J 733 647 554 606 549 485 716 669 568 633<br />

<strong>ESW</strong> 144-26K 777 687 587 645 583 516 756 704 601 674<br />

<strong>ESW</strong> 144-33I 577 510 431 470 422 373 552 515 435 484<br />

<strong>ESW</strong> 144-33J 617 544 460 503 453 401 586 547 463 514<br />

<strong>ESW</strong> 144-33K 651 573 484 531 476 423 614 573 486 540<br />

<strong>ESW</strong> 144-33L 680 594 502 556 498 443 640 592 504 562<br />

<strong>ESW</strong> 144-34I 641 564 483 527 474 418 618 576 493 545<br />

<strong>ESW</strong> 144-34J 692 608 521 568 511 453 662 615 527 584<br />

<strong>ESW</strong> 144-34K 730 643 547 600 543 480 697 648 552 615<br />

<strong>ESW</strong> 144-34L 765 675 571 630 569 502 725 678 575 643<br />

COOLER CAPABILITY IN USGPM AT THE FOLLOWING TEMPERATURE CONDITIONS (°F)<br />

EWT 100° 100° 97° 115° 115° 100° 102° 105° 105° 105°<br />

LWT 85° 85° 87° 90° 90° 90° 90° 90° 90° 90°<br />

Model No. WB 74° 76° 78° 74° 76° 80° 78° 76° 78° 80°<br />

<strong>ESW</strong> 144-23I 404 356 500 386 357 559 555 516 469 413<br />

<strong>ESW</strong> 144-23J 433 381 533 412 381 595 590 550 499 442<br />

<strong>ESW</strong> 144-23K 454 399 559 432 399 621 615 575 520 461<br />

<strong>ESW</strong> 144-24I 455 399 557 437 405 629 624 583 530 470<br />

<strong>ESW</strong> 144-24J 489 431 599 470 436 676 667 623 567 502<br />

<strong>ESW</strong> 144-24K 514 454 628 494 458 706 698 654 594 527<br />

<strong>ESW</strong> 144-25I 494 434 604 481 443 686 678 633 578 512<br />

<strong>ESW</strong> 144-25J 534 473 652 519 481 733 727 683 622 552<br />

<strong>ESW</strong> 144-25K 564 498 687 547 507 771 763 716 652 580<br />

<strong>ESW</strong> 144-26I 526 463 644 516 476 727 722 674 617 549<br />

<strong>ESW</strong> 144-26J 570 504 696 561 518 781 777 727 666 592<br />

<strong>ESW</strong> 144-26K 603 537 732 592 550 822 815 767 701 624<br />

<strong>ESW</strong> 144-33I 432 381 533 412 381 594 589 549 498 442<br />

<strong>ESW</strong> 144-33J 461 405 568 438 405 631 625 584 528 467<br />

<strong>ESW</strong> 144-33K 483 425 591 458 424 660 652 610 552 488<br />

<strong>ESW</strong> 144-33L 503 443 612 475 440 684 678 632 573 506<br />

<strong>ESW</strong> 144-34I 488 430 598 469 435 675 666 622 566 501<br />

<strong>ESW</strong> 144-34J 524 462 639 503 466 716 709 664 603 537<br />

<strong>ESW</strong> 144-34K 553 487 674 530 491 750 744 698 632 563<br />

<strong>ESW</strong> 144-34L 578 507 700 553 513 780 773 726 659 586<br />

Notes:<br />

1. Conditions are based on WATER as the Cooling Fluid.<br />

2. CTI Certified performance capability based on Standard and Super Low Sound Fan.<br />

3. For more CTI Certified selections, consult EVAPCO’s iES Selection Program.<br />

4. High flow header connections may be required for some flow rates.<br />

* Flow outside limits allowed for model.<br />

† Mark owned by the Cooling Technology Institute.<br />