Filter elements<br />

Filter class<br />

F6<br />

F8<br />

F6 F7 F9<br />

F6 F7 F9<br />

Designation<br />

MULTITHERM<br />

MULTIPLAN<br />

MULTI 2004<br />

Type<br />

60 90<br />

65 85 95<br />

MF65 MF85 MF95<br />

Regenerable<br />

No<br />

No<br />

No No No<br />

No No No<br />

Form of delivery *<br />

The filter medium consists of deeply<br />

The filter medium used is special,<br />

The steel frame is corrosion-resi-<br />

folded, paper-like micro-fibre fleece.<br />

paper-like fleece made of superfine<br />

stant as a result of an RAL 9011<br />

The position of the folds is stabilised<br />

micro-glass fibres, which are<br />

surface finish. In the system frame,<br />

either by wave-shaped aluminium<br />

processed to form a stable package<br />

the filter inserts are inserted with a<br />

separators, or by filter-material strips<br />

of folds. As standard version, the<br />

magnetic-strip seal, in V shape. The<br />

to separate the folds. The filter<br />

filter element is provided with a<br />

pleated filter packs are glued<br />

package is inserted dry in a filter<br />

peripheral seal on the intake<br />

airtight in a moisture-resistant<br />

frame made of sendzimir-galvanised<br />

(dusty)-air side. The filter frame is<br />

carton frame.<br />

sheet steel, with grip protection on<br />

made of MDF.<br />

both sides. All materials satisfy<br />

stipulations pertaining to the absence<br />

of silicone, and are temperature<br />

resistant up to 250°C.<br />

Technical filter data<br />

in accordance with DIN EN 779<br />

These plots are valid for<br />

size 610 x 610 mm for MULTITHERM;<br />

otherwise, for 592 x 592 mm.<br />

Pressure drop (Pa)<br />

200<br />

160<br />

120<br />

80<br />

40<br />

MT-90-T<br />

MT-60-T<br />

Pressure drop (Pa)<br />

200<br />

160<br />

120<br />

80<br />

40<br />

MP-85<br />

MP-95<br />

MP-65<br />

Pressure drop (Pa)<br />

250<br />

200<br />

150<br />

100<br />

50<br />

MF-95<br />

MF-85<br />

0<br />

0 850 1700 2550 3400 4250<br />

Air volume (m³/h*m²)<br />

0<br />

0 750 1500 2250 3000<br />

Air volume (m³/h*m²)<br />

MF-65<br />

0 0 850 1700 2550 3400 4250<br />

Air volume (m³/h*m²)<br />

Mean degree of separation (%)<br />

As per DIN EN 779<br />

Mean filter efficiency (%)<br />

Max. allowed pressure drop (Pa)<br />

Operating temperature (max. °C)<br />

> 98 > 98<br />

60.5 90.5<br />

450 450<br />

250 250<br />

98 > 99 > 99<br />

60 80 95<br />

450 450 450<br />

80 80 80<br />

> 98 > 98 > 98<br />

60 80 95<br />

450 450 450<br />

80 80 80<br />

Installation depth / thickness (mm)<br />

40 / 55 / 78 / 292 –<br />

46 / 78 / 150 / 292 – –<br />

304 304 304<br />

Flat seal<br />

+6 –<br />

+8 – –<br />

– – –<br />

PR-2009-0047-GB · We reserve the right to make changes without notice · Version: 02/2009<br />