Note: Please contact HygroMatik if you wish to operate the unit<br />

with softened water.<br />

• If using a water softening system, we recommend diluting<br />

the softened water with normal tap water to produce<br />

an overall hardness between 4-8°dH.<br />

• When feed water contains softened water, the level of<br />

conductivity is typically higher at operating temperature.<br />

Install a HygroMatik "cylinder star" to extend the service<br />

life of the electrodes.<br />

6.2 Water Supply<br />

» Install a shut-off valve (SV) in the supply line.<br />

» Install a water filter (WF) if water quality requires it.<br />

Note: Shut-off valve (SV) and water filter (WF) are not supplied<br />

with the unit<br />

» HygroMatik provides a water hose (56) with a cap nut at<br />

both ends which can be used for water installation.<br />

Install as follows:<br />

» Screw and tighten the cap nut with its inner seal ring<br />

around the water supply screw connection that protrudes<br />

from the base.<br />

Note: Tightening too much will destroy the fitting. The valve<br />

strainer (29) must be placed inside the solenoid valve.<br />

» Use a cap nut (internal thread ¾“) with inner seal for a<br />

customer-provided water installation.<br />

Page 19