» Remove cylinder, as described in Chapter 8.3 "Removing<br />

and Cleaning <strong>Steam</strong> Cylinder."<br />

» Loosen knurled nuts (5) and remove electrodes (48).<br />

» Install new electrodes and hand tighten the nuts.<br />

» Use solvent-free, HygroMatik-quality o-rings (for flange,<br />

cylinder base and steam hose adapter).<br />

» assemble steam cylinder and place it into housing.<br />

» Connect plugs (4) directly to the electrodes (48) (with<br />

gray, red and black knurled nuts). It is not necessary to<br />

detach the knurled nuts!<br />

Warning: The plug must be pressed down onto the electrode as<br />

far as it will go.<br />

Note: Connect plugs to the correct electrodes. Pay attention to<br />

the color of the knurled nut.<br />

» Attach plug (8) to the sensor electrode. < (Knurled nut<br />

(9) - gray)<br />

» Switch breaker back on.<br />

» Switch on the unit and check for leaks after 15-30 minutes<br />

of operation.<br />

If leakage occurs, switch off power supply and follow safety<br />

instructions for work on live components.<br />

Note: In the following cases:<br />

• the electrodes must be frequently replaced,<br />

• black slime collects inside the cylinder, or<br />

• there is "lightning" in the cylinder,<br />

the conductivity of the water is too high or it isn't decanted often<br />

enough. In this case please contact HygroMatik.<br />