9.4.2 Uneven <strong>Electrode</strong> Lengths<br />

In most case, the longer electrode(s) will not be supplied with<br />

electricity for a time. Therefore they will not wear. The cause of<br />

the problem, such as a tripped circuit breaker, can be repaired.<br />

However, since the shorter electrode(s) have a greater specific<br />

load, the electrodes continue to wear unevenly.<br />

Note: Replace electrodes with significantly uneven wear. Check<br />

the power supply (breaker, voltage drop). Also see electronic<br />

operation, Section "Malfunctions."<br />

9.5 Replacing <strong>Electrode</strong>s<br />