Cycle<br />

4 Weeks after<br />

initial operation<br />

(with normal<br />

water quality)<br />

Semiannually<br />

(with normal<br />

water quality and<br />

"normal" operation<br />

= 8h/Day)<br />

Maintenance Work<br />

Visual inspection of electrical and<br />

mechanical connections<br />

Remove mineral deposits from steam cylinder,<br />

water drain hose and blow-down<br />

pump<br />

Check electrodes for erosion<br />

Visual inspection of electrical and<br />

mechanical connections<br />

Remove mineral deposits from steam cylinder,<br />

water drain hose and blow-down<br />

pump<br />

und ggf. erneuern.Check electrodes for<br />

erosion<br />

In most cases, the conductivity levels given in Section 1.1<br />

"Directions for Use" of these instructions can be considered normal.<br />

Individual parameter setting of the control may be necessary.<br />

In extreme cases, water pretreatment may be necessary (softening<br />

by dilution to approx. 4 - 8 °dH; decarbonization/partial<br />

desalination to achieve target reductions in carbonate hardness).<br />

HygroMatik would be pleased to refer you to companies specializing<br />

in water treatment systems.<br />

9.2 Access Electrical Enclosure<br />

» Remove cover from humidifier (B) and lift display plate<br />

(A) of guiding.<br />

» Turn display plate (please see sketch) and hang up display<br />

plate by using the „front guiding“.<br />

» The basic PCB (C) is now accessable.<br />

Danger, Hazardous Voltage: Make sure the unit is switched off<br />

before installing or removing the display plate.<br />