20.11.2014 Views

What is TRUFLOW? - Spring Air Systems Inc.

What is TRUFLOW? - Spring Air Systems Inc.

What is TRUFLOW? - Spring Air Systems Inc.

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Truflow<br />

Touchscreen<br />

Engineering<br />

Manual<br />

___________________________<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>Inc</strong>., Oakville, Ontario<br />

Phone (866) 875-4505, Fax (905) 338-0179, info@springairsystems.com<br />

www.springairsystems.com<br />

December 2007


Engineering Manual<br />

Table of Contents<br />

Introduction 1<br />

<strong>What</strong> <strong>is</strong> Truflow? 3<br />

Why Use Truflow? 3<br />

How Many Hoods Can Be Connected to Each Exhaust Fan? 5<br />

Design Tips to Maximize Energy Savings 7<br />

How Does the Truflo Work? 8<br />

SV Supply Control 13<br />

SC Supply Control 15<br />

Activation Control Options 18<br />

Sequence of Operation 19<br />

Activating Kitchen One 19<br />

Summer Winter Operation 20<br />

Override 21<br />

Surface Fire Suppression 21<br />

Multiple Kitchen Operation 22<br />

Setting Goals 23<br />

Option Wireless Remote 24<br />

Appendix A Minimum Duct Velocity in the Building Code 25<br />

Appendix B Truflo Panel Model Number 26<br />

Appendix C Hood mounted Truflow Enclosure 27<br />

Appendix D Wall mounted Truflow Enclosure 28<br />

Appendix E Installation and Remote Wiring 29<br />

Appendix F Sample Specification 33<br />

Nov19


<strong>TRUFLOW</strong> Engineering Manual<br />

SEE WHAT YOU SAVE<br />

Introduction<br />

Prec<strong>is</strong>e, real-time measurement so you can effectively manage your team to reduce<br />

energy use.<br />

<strong>TRUFLOW</strong> DASHBOARD<br />

Figure 1<br />

Truflow <strong>is</strong> the most economical<br />

and efficient kitchen ventilation<br />

energy management system<br />

available.<br />

The average commercial kitchen<br />

exhaust system operates at 100%<br />

capacity for 12 to 18 hours per day,<br />

blowing thousands of wasted<br />

energy dollars out the roof!<br />

Truflow measures heat from the<br />

appliances and automatically<br />

adjusts fan speeds throughout the<br />

day, giving you the prec<strong>is</strong>e amount<br />

of exhaust at all times.<br />

Truflow monitors ventilation system efficiency relative to your utility costs, in real-time,<br />

so that you can manage your kitchen to take advantage of off peak times by turning down<br />

appliances. Setting an energy reduction goal reduces your utility costs even more!<br />

You have the ability to increase the exhaust volume to 100% at any time. Because you<br />

control it, overrides are kept to a minimum to maximize energy efficiency. The override<br />

system runs for an adjustable timed period of 15 minutes and can be activated at the hood<br />

or via a remote control.<br />

Truflow not only saves you money on energy expenses it can also help extend the life of<br />

your equipment by demanding exhaust only when it <strong>is</strong> really required. Truflow can be<br />

specified on new hoods or can be retrofitted on you ex<strong>is</strong>ting hoods. Since the panel can<br />

be hood mounted or wall mounted, it allows many convenient options of where to locate<br />

the panel and wireless remote unit. Truflow <strong>is</strong> internet accessible, so it <strong>is</strong> ideal for multiunit<br />

management.<br />

The <strong>TRUFLOW</strong> system reduces the amount of air exhausted from the kitchen to match<br />

the amount of cooking. As more appliances are used, the exhaust and supply volume<br />

increase, as less appliances are used the exhaust and supply volume decreases.<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 1


185<br />

Benefits:<br />

• Lower energy costs to boost profit<br />

• Improve kitchen air quality<br />

• Reduce kitchen fan no<strong>is</strong>e<br />

• Extend the life of your equipment<br />

• Internet accessible for remote management<br />

• Semi-automatic override to maximize energy efficiency<br />

Exhaust Fan<br />

Roof Deck<br />

Exhaust Duct<br />

Fin<strong>is</strong>hed Ceiling<br />

J-COUPLE<br />

Exhaust Hood<br />

Touchscreen<br />

Fin<strong>is</strong>hed Floor<br />

Appliance Lineup<br />

<strong>TRUFLOW</strong> Setup screen<br />

Figure 3<br />

Typical <strong>TRUFLOW</strong> Kitchen<br />

Figure 2<br />

The <strong>TRUFLOW</strong> setup screen <strong>is</strong> shown in<br />

Figure 3 for the single kitchen above.<br />

The kitchen has one exhaust fan with one<br />

supply fan operating with a VSD<br />

(Variable Speed Drive). RSS (Remote<br />

Start Stop) has not been selected so the<br />

<strong>TRUFLOW</strong> will operate locally. KES<br />

has not been selected so the fan <strong>is</strong> a<br />

straight exhaust with no Kitchen Enviro<br />

System selected. In addition there <strong>is</strong> no<br />

WASH selected so there <strong>is</strong> no automatic<br />

wash type hood connected to th<strong>is</strong> kitchen.<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 2


<strong>What</strong> <strong>is</strong> <strong>TRUFLOW</strong>?<br />

The <strong>TRUFLOW</strong> Energy Management Controller has been designed to change kitchen<br />

exhaust forever. <strong>TRUFLOW</strong> will automatically reduce the exhaust and supply air into<br />

the kitchen whenever appliances are not used at full capacity. When the appliances are<br />

not used and the heat <strong>is</strong> turned down or off <strong>TRUFLOW</strong> automatically senses the<br />

reduction and decreases the amount of exhaust and supply to match exactly what’s<br />

happening under the exhaust hood. The <strong>TRUFLOW</strong> duct mounted J-Couple monitors the<br />

exhaust temperature, which fluctuates based on the amount of appliances operating under<br />

the exhaust hood. As the amount of cooking increases the exhaust duct temperature r<strong>is</strong>es<br />

and reaches an equilibrium temperature during each hour of the day. Th<strong>is</strong> equilibrium<br />

temperature represents a percentage of total cooking capacity. The 30% utilization<br />

temperature may be 80F. The 70% utilization temperature may be 105F. The duct<br />

temperature could reach as high as 150F and as low 75F depending on the following<br />

factors:<br />

• Kitchen room temperature<br />

• Total exhaust volume<br />

• BTU rating of each appliance<br />

• Total volume of makeup air<br />

• Temperature of makeup air<br />

• Where the makeup air <strong>is</strong> introduced back into the kitchen<br />

• Type of hood over the appliance<br />

<strong>TRUFLOW</strong> automatically modulates the exhaust and supply to suit the actual cooking<br />

operation at any given time during the cooking day.<br />

Why Use a <strong>TRUFLOW</strong>?<br />

Energy Savings up to 55% annually! Reduces operating cost.<br />

Let’s take a look at Chart No 1. The <strong>TRUFLOW</strong> does not lower the exhaust volume<br />

below 30% of the maximum operating exhaust. For the purpose of th<strong>is</strong> chart we add<br />

operating times below 30% into the 30% operating time.<br />

Appliance Operating Capacity<br />

% of full appliance load that kitchen <strong>is</strong> operating at<br />

Operating Time<br />

% of time that kitchen <strong>is</strong> operating at stated Appliance<br />

Operation Capacity<br />

Hours of 16 hour day Number of hours, out of a 16 hour day, equating to %<br />

shown in Operating Time<br />

Equivalent CFM<br />

Calculated as Total Exhaust CFM x (%Appliance<br />

Operating Capacity) x (%Operating Time)<br />

Based on 4500 CFM total exhaust volume from our example above, the chart <strong>is</strong> tabulated.<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 3


Typical Commercial Kitchen Operation with <strong>TRUFLOW</strong><br />

Appliance<br />

Operation<br />

Capacity (%)<br />

Operating Time<br />

(%)<br />

Hour of 16 hour<br />

day<br />

Equivalent<br />

CFM<br />

30 30 4.8 405<br />

40 10 1.6 180<br />

50 10 1.6 225<br />

60 5 0.8 135<br />

70 10 1.6 315<br />

80 5 0.8 180<br />

90 10 1.6 405<br />

100 20 3.2 900<br />

Equivalent Daily Exhaust Volume CFM<br />

2745 CFM<br />

Semi Automatic Design<br />

<strong>TRUFLOW</strong> <strong>is</strong> a semi automatic design because of the manual OVERRIDE pushbutton.<br />

In the unlikely event that smoke does leak from the edge of the hood the operator simply<br />

pushes the OVERRIDE pushbutton to drive the exhaust volume to 100% for 15 minutes.<br />

After 15 minutes the exhaust automatically reverts back to temperature based control.<br />

(The 15 minutes override time <strong>is</strong> adjustable on the Touchscreen.) The smoke generated<br />

from appliances sometimes lags the duct temperature r<strong>is</strong>e because of the following:<br />

• Large quantities of greasy foods are tossed on the grille at one time.<br />

• A large tilting skillet or kettle <strong>is</strong> opened quickly or<br />

• A draft from a door or window opening.<br />

The <strong>TRUFLOW</strong> <strong>is</strong> comm<strong>is</strong>sioned by a <strong>Spring</strong> <strong>Air</strong> service<br />

technician to minimize these OVERRIDE events. The kitchen <strong>is</strong><br />

put into override by pressing the efficiency button on the<br />

Touchscreen Dashboard.<br />

Efficiency Button<br />

Figure 4<br />

From the Dashboard press the EFFICIENCY button to set the<br />

Truflow into override operation. The kitchen exhaust will operate<br />

at 100% volume for the time set on the override timer.<br />

To select the Override time, go to the System Control screen and<br />

press the O/R button. A second screen will open.<br />

The Override time <strong>is</strong> adjustable from the System Control screen by<br />

pressing the O/R button. The time <strong>is</strong> adjustable from 0 to 240<br />

minutes with a factory default of 15 minutes.<br />

Efficiency Button in Override<br />

Figure 5<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 4


How many hoods can be connected to each exhaust fan?<br />

Truflow Setup Screen<br />

Figure 6<br />

Each <strong>TRUFLOW</strong> Touchscreen <strong>is</strong><br />

capable of operating five independent<br />

kitchens, six exhausts and/or supply<br />

fans with up to 10 commercial<br />

kitchen hoods per exhaust fan. The<br />

number of exhaust fans <strong>is</strong> determined<br />

by the operational requirements of the<br />

kitchen appliances under each hood.<br />

When three hoods and two exhaust<br />

fans are connected as one kitchen any<br />

change in appliance usage under any<br />

of the three hoods will result in<br />

increasing the volume of the two<br />

exhaust fans. The optimum Truflow<br />

method to maximize savings <strong>is</strong> to<br />

operate the <strong>TRUFLOW</strong> Touchscreen<br />

with two kitchens cons<strong>is</strong>ting of one<br />

exhaust fan and one hood, and one exhaust fan and two hoods. The two kitchens operate<br />

completely independently supplying a single 4-20 milliamp signal to one makeup air unit.<br />

Truflow Setup Screen –Two Kitchens<br />

– two exhaust 4-20 milliamp supply signal<br />

Figure 7<br />

The schematic below shows a<br />

restaurant with one exhaust fan with<br />

one hood and one exhaust fan with two<br />

hoods. Th<strong>is</strong> should be operated by the<br />

Truflow as two kitchens. Kitchen One<br />

cons<strong>is</strong>ts of one exhaust fan and one<br />

hood. Kitchen Two cons<strong>is</strong>ts of one<br />

exhaust fan and two exhaust hoods.<br />

The restaurant could have one or two<br />

makeup air units. One makeup air unit<br />

could be controlled by both kitchens or<br />

each kitchen could control a separate<br />

makeup air unit. Energy savings with<br />

one or two makeup air units would be<br />

similar.<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 5


185<br />

185<br />

Exhaust Fan<br />

Exhaust Fan<br />

Roof Deck<br />

Roof Deck<br />

Exhaust Duct<br />

Exhaust Duct<br />

Fin<strong>is</strong>hed Ceiling<br />

Fin<strong>is</strong>hed Ceiling<br />

Exhaust Hood<br />

Exhaust Hood #1<br />

Exhaust Hood #2<br />

SYSTEMS ONE: ONE EXHAUST FAN ONE HOOD<br />

SYSTEM TWO: ONE EXHAUST FAN/TWO HOODS<br />

Kitchen 1: One hood and one exhaust fan, Kitchen two: Two hoods with<br />

one exhaust fan. Both Kitchens control a single makeup air unit.<br />

Figure 8<br />

<strong>TRUFLOW</strong> System Control Screen for Operation: Two<br />

Kitchens, Two exhausts, Two supply 4-20 milliamp signals<br />

Figure 9<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 6


185<br />

185<br />

185<br />

185<br />

SV<br />

°F<br />

C1<br />

C2<br />

AL 1 1 1 0<br />

AL 2<br />

SEL<br />

SPR I NG AI R<br />

SUMMER /WINTE R C AN O PY L I GH TS<br />

EX HAU ST<br />

OCC UPIED/UNOCCUPIED<br />

SU PPLY<br />

OPE RA TION<br />

TRU-FLO VARI ABLE CONTROL<br />

HI<br />

PUSHTO OVERIDE<br />

Exhaust Fan<br />

Exhaust Fan<br />

Exhaust Fan<br />

Exhaust Fan<br />

Roof Deck<br />

Roof Deck<br />

Roof Deck<br />

Roof Deck<br />

Exhaust Duct<br />

Exhaust Duct<br />

Exhaust Duct<br />

Exhaust Duct<br />

Exhaust Hood #1<br />

Exhaust Hood #2<br />

Exhaust Hood #3<br />

Exhaust Hood #4<br />

SYSTEM ONE: 1 EXHAUST, ONE HOOD<br />

SYSTEM TWO: 1 EXHAUST, ONE HOOD<br />

SYSTEM THREE: 1 EXHAUST, ONE HOOD<br />

SYSTEM FOUR: 1 EXHAUST, ONE HOOD<br />

Four Kitchens with one hood and one exhaust fan each. One 4-20 milliamp signal <strong>is</strong><br />

send to one single makeup air unit based on the combined exhaust volume.<br />

Figure 10<br />

<strong>TRUFLOW</strong> Setup screen for Operation: Four Kitchens,<br />

Four exhausts, Four supply 4-20 milliamp signals<br />

Figure 11<br />

Design Tips to Maximize Energy Savings<br />

• Connect each hood to an exhaust fan whenever possible or as the budget allows.<br />

• For each Truflow Touchscreen use as many sub Kitchens as possible for each<br />

individual hood and exhaust fan operation.<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 7


How does the <strong>TRUFLOW</strong> Work?<br />

The <strong>TRUFLOW</strong> cons<strong>is</strong>ts of three primary components:<br />

1. J-couple.<br />

2. Touchscreen<br />

3. Variable Speed Drives<br />

1. J-COUPLE<br />

The J-couple <strong>is</strong> mounted in the center of each exhaust hood duct collar. The J-couple<br />

threads into a UL/ULC l<strong>is</strong>ted hood penetration fitting. The J-couple wiring <strong>is</strong> terminated<br />

in a factory supplied J-Box.<br />

J-couple Mini-Clip connector to the Truflo panel<br />

UL/ULC duct penetration fitting<br />

J-box<br />

Exhaust duct collar<br />

J-couple<br />

Exhaust Hood<br />

2. TOUCHSCREEN<br />

J-Couple hood duct collar mounting<br />

Figure 12<br />

Touchscreen Dashboard<br />

Figure 13<br />

The Touchscreen includes five functional screens: Dashboard, System Control, Alarm<br />

Status, Reports and Setup & Diagnostics.<br />

a. Dashboard<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 8


• Graph represents energy use throughout<br />

day<br />

• Energy consumption measured against<br />

reduction goal<br />

• Dashboard tells kitchen staff whether<br />

system exceeding goal or not.<br />

• Exhaust CFM, duct and outdoor<br />

temperature d<strong>is</strong>played<br />

• Outdoor temperature measurement<br />

allows for real-time energy savings<br />

reports directly from TruFlow!<br />

Touchscreen Dashboard<br />

Figure 14<br />

b. System Control<br />

• D<strong>is</strong>plays components of all exhaust<br />

systems controlled by TruFlow<br />

– Hood lights<br />

– Fan on/off<br />

– Summer/winter switch<br />

– Override<br />

c. Alarm Status<br />

Touchscreen System Control<br />

Figure 15<br />

• Alarm conditions d<strong>is</strong>played for all<br />

systems controlled by TruFlow<br />

• Touch single bell icon to clear selected<br />

alarm<br />

• Touch multi-bell icon to clear all alarms<br />

• Th<strong>is</strong> action does not FIX the problem it<br />

simply records that an alarm or alarms<br />

have been acknowledged.<br />

• Service Company must still be called!<br />

Touchscreen Alarm Status<br />

Figure 16<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 9


d. Alarm Condition<br />

• On alarm, d<strong>is</strong>play changes to alarm<br />

with optional audible alert<br />

• Touchscreen to go to Alarm Status<br />

Screen<br />

• Touching screen records action in<br />

event log<br />

e. Reports<br />

Alarm Condition Screen<br />

Figure 17<br />

• TruFlow can record a full year of data<br />

• Standard reports provided<br />

• Can create custom reports depending<br />

on needs of user<br />

• % Time Exceeding Goal <strong>is</strong> a key<br />

energy management report<br />

f. Setup & Diagnostics<br />

Touchscreen Reports<br />

Figure 18<br />

• Main system setup d<strong>is</strong>play allows<br />

entry of reduction goal, primary<br />

message center text and company or<br />

restaurant name<br />

• Power of TruFlow lies in the setting of<br />

an energy reduction goal<br />

• Goal represents a target % reduction of<br />

past utility costs (hourly or monthly<br />

rate)<br />

Touchscreen Setup<br />

Figure 19<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 10


• Goal can be reset at any time to maximize energy efficiency and savings!<br />

• Gas and electricity costs can be entered at any time as monthly or hourly rates<br />

• Measure gas in joules or therms by selecting Imperial or Metric Units<br />

• Set daily or weekly operating times<br />

• Permits<br />

• Comprehensive service screen to quickly diagnose problems<br />

• Can access via Internet for remote service by <strong>Spring</strong> <strong>Air</strong> directly or Authorized<br />

Service Technician<br />

3. VARIBLE SPEED DRIVES<br />

The variable speed drives for the exhaust and/or supply fan can be located in a<br />

stainless steel enclosure adjacent to the Touchscreen panel or anywhere else in the<br />

building.<br />

• When direct gas fire unit <strong>is</strong> part of <strong>TRUFLOW</strong> the supply drive can be located<br />

in the makeup air unit control panel or with the exhaust fan drive(s) (SV<br />

Type)<br />

• When a SFA-IGO unit <strong>is</strong> part of <strong>TRUFLOW</strong>, a supply drive <strong>is</strong> not required.<br />

The Touchscreen panel sends a 4-20milliamp signal through a CAT5 cable to<br />

the makeup air unit modulating bypass damper. (SC Type)<br />

Two exhaust drives and one supply drive connected to the Touchscreen panel<br />

Figure 20<br />

A CAT5 cable <strong>is</strong> connected to each drive in series from the Touchscreen panel. The<br />

first cable connects from the Touchscreen to the first drive “Y” connector. The 2 nd<br />

drive cable connects from the first drive “Y” connector to the 2 nd drive “Y”<br />

connector. Each drive <strong>is</strong> connected in series. When the Touchscreen <strong>is</strong> initially<br />

activated the communication software starts all the exhaust and/or supply drive at<br />

100% capacity for 10 seconds for each kitchen. After the initial 10 seconds the<br />

exhaust and/or supply drives ramp up and down depending on the signal from the J-<br />

couple(s). As the exhaust volume increases and decreases, the supply volume<br />

increases and decreases in un<strong>is</strong>on to maximize energy savings. The supply unit<br />

motorized damper end switch can also be interlocked to the Touchscreen such that the<br />

end switch must close to start the supply fan drive operation.<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 11


The drive changes the AC<br />

to the exhaust motor between 18Hz<br />

frequency<br />

and 60Hz.<br />

Variable Speed Drive<br />

Figure 21<br />

Variable Speed Drive Field Wiring<br />

Figure 22<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 12


SV Supply Control<br />

<strong>TRUFLOW</strong> Operation with SV Control for the following applications:<br />

• SAT direct gas fired supply units<br />

• Other direct gas fired supply units with unit mounted variable speed drive VSD<br />

• Supply units with electric heating, hot water heating, or no heating or cooling<br />

The Touchscreen receives a signal from the duct mounted J-couple that controls the<br />

exhaust motor VSD. The exhaust motor variable speed drive slows or speeds up the<br />

exhaust fan motor to maintain the required exhaust volume to match the amount of<br />

cooking. Simultaneously the Truflow controls the <strong>Spring</strong> <strong>Air</strong> SAT supply fan motor or<br />

other supply fan motors supplied by others. The supply variable speed drive changes the<br />

frequency of the supply fan motor to modulate the supply air into the kitchen space in<br />

proportion to the exhaust air volume.<br />

Exhaust<br />

Fan<br />

SUPPLY FAN<br />

CAT5 Variable Speed<br />

drive signal to motor<br />

CAT5 Variable Speed<br />

Drive signal to motor<br />

J-Couple<br />

Kitchen Hood<br />

SV- Supply Volume Control with Variable Speed Supply Drive<br />

Figure 23<br />

The lowest possible exhaust volume <strong>is</strong> 30% of the maximum to meet the ex<strong>is</strong>ting code<br />

and to ensure that the products of combustion are always completely exhausted.<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 13


185<br />

185<br />

100%<br />

<strong>Spring</strong> <strong>Air</strong> SAT (Direct Gas Fired Makeup <strong>Air</strong> Unit)<br />

J-couple<br />

Exhaust Hood<br />

<strong>TRUFLOW</strong><br />

TOUCHSCREEN<br />

<strong>TRUFLOW</strong> System operating at 100% with SAT direct gas fired makeup with SV control<br />

Figure 24<br />

30%<br />

<strong>Spring</strong> <strong>Air</strong> SAT (Direct Gas Fired Makeup <strong>Air</strong> Unit)<br />

J-couple<br />

Exhaust Hood<br />

<strong>TRUFLOW</strong><br />

TOUCHSCREEN<br />

<strong>TRUFLOW</strong> operating at 30% with SAT direct gas fired makeup with SV control<br />

Figure 25<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 14


<strong>TRUFLOW</strong> – One Kitchen – Two exhaust fans – One supply fan – Six hoods<br />

Figure 26<br />

SC Supply Control<br />

<strong>TRUFLOW</strong> Operation with SC Control for the following applications:<br />

• SFT-IGO fresh air unit with heating or DX cooling<br />

• A 4-20 milliamp signal to Building Management System to control fresh air with<br />

HVAC bypass dampers<br />

• A 4-20 milliamp signal to a fresh air makeup air unit to modulate fresh air/return<br />

air bypass damper(s)<br />

Truflow receives signals from the J-couple and transmits a signal along a CAT5 cable to<br />

the exhaust motor VSD. The exhaust motor variable speed drive slows or speeds up the<br />

exhaust fan to maintain the required exhaust volume depending on the amount of<br />

cooking. At the same time, Truflow sends a 4-20 milliamp signal to the <strong>Spring</strong> <strong>Air</strong> SFT<br />

supply unit modulating Bypass <strong>Air</strong> damper. Th<strong>is</strong> bypass damper modulates to bypass<br />

fresh air from the supply air d<strong>is</strong>charge back to the SFT fan section.<br />

The lowest possible exhaust volume <strong>is</strong> 30% of the maximum to meet the ex<strong>is</strong>ting code<br />

and ensure that the products of combustion are always adequately exhausted.<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 15


Exhaust<br />

Fan<br />

CAT5 Variable Speed<br />

drive signal to motor<br />

4-20 milliamp Signal to<br />

Bypass Damper Motor<br />

J-Couple<br />

Signal<br />

Kitchen Hood<br />

SV- Supply Volume Control with Variable Speed Supply Drive<br />

Figure 27<br />

Truflow – One exhaust fan – One 4-20 milliamp supply signal – Three hoods<br />

Figure 28<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 16


185<br />

185<br />

100%<br />

<strong>Spring</strong> <strong>Air</strong> SFT<br />

Blend <strong>Air</strong> Channel<br />

J-couple<br />

Exhaust Hood<br />

<strong>TRUFLOW</strong><br />

<strong>TRUFLOW</strong> operating at 100%. No Bypass required on <strong>Spring</strong> <strong>Air</strong> SFT<br />

Figure 29<br />

30%<br />

<strong>Spring</strong> <strong>Air</strong> SFT<br />

BYPASS <strong>Air</strong><br />

J-couple<br />

Exhaust Hood<br />

<strong>TRUFLOW</strong><br />

<strong>TRUFLOW</strong> operating at 30%. Notice the bypass air below the on <strong>Spring</strong> <strong>Air</strong> SFA<br />

Figure 30<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 17


Activation Control Options<br />

There are four separate <strong>TRUFLOW</strong> Operation Control options: Manual Control at the<br />

panel, Automatic Control using panel auto function, Remote Start/Stop Control with dry<br />

contact, and BACnet or LON control directly to the <strong>TRUFLOW</strong> PLC.<br />

1. Manual Control:<br />

Press the System Control button<br />

to switch to the screen<br />

Press the Hand button to switch<br />

to manual mode.<br />

Each kitchen <strong>is</strong> turned on by<br />

pressing the Fan button. Active<br />

button has white border.<br />

When the fan <strong>is</strong> on the fan<br />

graphic icon <strong>is</strong> moving.<br />

System Control screen<br />

Figure 31<br />

Pressing the button again turns<br />

off the kitchen operation.<br />

2. Automatic Control:<br />

Press the Setup button to<br />

change to the System Setup<br />

screen<br />

Press the Fan Time button to<br />

change to the Kitchen<br />

Operation screen. Select the<br />

Operation time or hours for each day<br />

of the week.<br />

Fan Time screen<br />

Figure 32<br />

Go to the System Control<br />

screen and press the Hand<br />

button off. The white border<br />

surrounding the button will d<strong>is</strong>appear<br />

and the operation <strong>is</strong> now in automatic<br />

mode. The kitchen on and off times<br />

will follow the time set on the Fan<br />

Time screen.<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 18


3. Remote Start/Stop:<br />

Setup screen RSS checked<br />

Figure 33<br />

Press the Setup button twice<br />

quickly to change to the<br />

secondary System Setup<br />

screen.<br />

Press the System<br />

Setup bar once and<br />

then Press the RSS<br />

button. The automatic mode as<br />

described above <strong>is</strong> d<strong>is</strong>abled and the<br />

RSS (Remote Start/Stop) function <strong>is</strong><br />

enabled. Closing a dry contact across<br />

terminals C+L will activate kitchen<br />

one. Closing a dry contact across<br />

terminals C2+CL will activate kitchen<br />

two…etc.<br />

4. BACnet or LON:<br />

The <strong>TRUFLOW</strong> panel can be operated directly from a BACnet or LON building<br />

management system. Connecting to the PLC through a RS234 connection will allow<br />

each kitchen to be operated from the Building Management System. The BMS can also<br />

read all information for the drives and panels. Truflow <strong>is</strong> LON compatible. An optional<br />

intermediate device can be supplied by <strong>Spring</strong> <strong>Air</strong> between the PLC and LON system to<br />

convert the various Truflow input and outputs to be recognized by the LON system.<br />

Sequence of Operation<br />

There are four separate <strong>TRUFLOW</strong> Operation Control options: Manual Control at the<br />

panel, Automatic Control using panel auto function, Remote Start/Stop Control with dry<br />

contact, and BACnet or LON control directly to the <strong>TRUFLOW</strong> PLC. See the section<br />

above for description of each method to activate the Truflow panel.<br />

At the start of the cooking day: Each kitchen connected to the Truflow panel <strong>is</strong> activated<br />

either manually, automatically, remotely or from a BACnet or LON.<br />

1. Activating Kitchen One<br />

All exhaust fans and supply fans connected to Kitchen One drive to 100% volume for 10<br />

seconds. After the initial 10 seconds each exhaust and supply return to normal mode.<br />

Normal mode <strong>is</strong> the exhaust and supply volume based on the number of appliances<br />

activated under the hoods served by the exhaust fans for Kitchen One. As more<br />

appliances are turned on or turned up, the hood duct J-couples sense the rate of change of<br />

duct temperature sending a signal to the Truflow to adjust the speed of the exhaust and<br />

supply fan motors.<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 19


Once the kitchen <strong>is</strong> turned on the dashboard graph <strong>is</strong> activated. The graph<br />

measures systems efficiency vs. seconds of operation.<br />

The system efficiency measures the<br />

operating efficiency of the kitchen as<br />

compared to the energy reduction goal<br />

set by kitchen management.<br />

In the example the real time<br />

operating efficiency <strong>is</strong> 75%.<br />

Th<strong>is</strong> means the kitchen <strong>is</strong><br />

operating at 75% of the energy savings<br />

goal.<br />

The Exhaust CFM <strong>is</strong> the<br />

actual total exhaust for<br />

Kitchen One.<br />

Dashboard Efficiency Graph<br />

Figure 34<br />

The Outside Temp <strong>is</strong> the actual outside temperature. Th<strong>is</strong> value <strong>is</strong> used to<br />

calculate the BTU’s of heating or cooling required for the kitchen. The BTU’s<br />

are converted to actual dollar cost and can be viewed from the Report screen.<br />

The light bulb turns the canopy light on and off.<br />

Press System Control to view<br />

other control options. Kitchen<br />

1 <strong>is</strong> the top row of symbols on<br />

the screen.<br />

The rotating fan icon indicates<br />

that the system <strong>is</strong> active.<br />

The light bulb can also be used<br />

to turn the canopy lights off<br />

and for the kitchen.<br />

System Control Screen<br />

Figure 35<br />

2. Summer/Winter<br />

The summer/winter symbol operation <strong>is</strong> connected to a Truflow dry contact across<br />

terminals 11+12. Pressing the icon on the System Control screen above changes the<br />

kitchen operation from summer to winter and back again.<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 20


Winter Operation: When the winter icon <strong>is</strong> d<strong>is</strong>played a Truflow dry contact closes.<br />

The icon <strong>is</strong> used in winter mode to turn off the (optional) makeup air cooling<br />

system and turn on the makeup air heating system. The Reports are now<br />

calculating the cost of heating the fresh air from the outside temperature to the<br />

room temperature or accumulating th<strong>is</strong> cost in chart form.<br />

Summer Operation: When the summer icon <strong>is</strong> indicated the Truflow dry contacts are<br />

open. The summer icon <strong>is</strong> used to turn off the makeup air heating system and<br />

activate the (optional) makeup air cooling system if it <strong>is</strong> present. The Reports are<br />

now calculating the electrical cost to operate a DX air conditioning system based<br />

on the difference between the outside dry bulb temperature and the inside dry bulb room<br />

temperature. The accumulated results are presented on the Report screen. When the A/C<br />

button located on the Setup/Goals screen <strong>is</strong> not selected the cost of summer kitchen<br />

cooling <strong>is</strong> not calculated and accumulated.<br />

3. Override<br />

Override Adjustment on System Control<br />

Figure 36<br />

Each Kitchen can be put into<br />

Override mode by pressing the<br />

EFFICIENCY button on the<br />

Dashboard of the individual<br />

kitchens. The factory override time <strong>is</strong><br />

set at 15 minutes.<br />

The override time can be<br />

adjusted from the System Control<br />

screen above. Pressing the O/R button<br />

to open a sub screen where the length of<br />

the override (in minutes) can be selected.<br />

4. Surface Fire Suppression<br />

The surface fire suppression <strong>is</strong> interlocked to th<strong>is</strong> panel from a micro switch located in<br />

the cylinder head of the fire suppression system. In the event of surface fire activation<br />

the micro switch closes across Truflow terminals B+L and the Truflow exhaust fans will<br />

continue to operate, the supply fans will shut off, and a 120V signal <strong>is</strong> sent to the shunt<br />

trip connected to the appliances under the hood with the activated surface fire<br />

suppression system. A panel alarm will annunciate. Press the screen and the alarm<br />

message will scroll across the bottom of the Truflow screen.<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 21


5. Multiple Kitchen Operation<br />

Press the Setup icon to switch to<br />

the First Setup screen.<br />

First Setup screen<br />

Figure 37<br />

Press Setup icon again on the<br />

first second setup screen to<br />

switch to the Second Setup screen.<br />

Second Setup screen<br />

Figure 38<br />

System Setup screen<br />

Figure 39<br />

Press the System Setup bar above to<br />

change to the screen on the left. First<br />

select the number of systems or<br />

Kitchens. Now select the number of<br />

exhaust fans for each system and then<br />

select whether the supply control will<br />

be by VSD or 4-20 milliamps. A<br />

unique name can be selected for each<br />

kitchen by touching the kitchen name.<br />

An on the system keyboard opens to<br />

allow the new name to be entered and<br />

stored in the Truflow.<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 22


Press the System Control icon to<br />

change screens. The System<br />

Control screen will d<strong>is</strong>play all four<br />

kitchens entered on the Setup screen.<br />

Each kitchen can be individually<br />

controlled from th<strong>is</strong> screen.<br />

Multiple System Control screen<br />

Figure 40<br />

Pressing the Dashboard icon<br />

shows the operation of each<br />

individual kitchen. Pressing the<br />

Kitchen name, Efficiency, or Exhaust<br />

CFM buttons will change the screen to the<br />

efficiency graph for the kitchen selected.<br />

6. Setting Goals<br />

Multiple Dashboard screen<br />

Figure 41<br />

Select the Setup icon to change<br />

the screen to the main setup<br />

screen. Th<strong>is</strong> screen would normally be<br />

locked and a password <strong>is</strong> required to see<br />

the next setup screen information as seen<br />

to the left.<br />

First Setup screen<br />

Figure 42<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 23


Reduction Goal Setup screen<br />

Figure 43<br />

Select the Dollar icon to change to<br />

the Energy Reduction Goal setup<br />

screen.<br />

The Energy Reduction Goal value <strong>is</strong> the<br />

percentage energy savings that the operator<br />

wants to achieve during normal operation of<br />

the kitchens. To save 20% annually, enter<br />

the number 20. The higher the percentage<br />

entered the more aggressive the energy<br />

savings goal. Next select the units imperial<br />

or metric. Enter the cost of gas in $/BTU’s.<br />

Enter the cost of electricity in $/KWH.<br />

Check Demand Electrical if the utility<br />

company has graduated billing throughout<br />

the day. Follow screen prompt to enter the demand cost of electricity and the time it<br />

takes effect. Finally select the A/C button if the kitchen <strong>is</strong> air conditioned with DX<br />

(Direct Expansion) cooling. If the kitchen <strong>is</strong> not air conditioned the summer energy cost<br />

will be only the cost of the exhaust and supply fan motors.<br />

Press the Dashboard icon to return to normal operation. The goal setting number shifts<br />

the ax<strong>is</strong> of the efficiency curve on the dashboard. A higher goal means the operation will<br />

run in the RED, or under 100% efficiency more often unless the kitchen operators are<br />

diligent at turning down or turning off appliances that are not in use. When the efficiency<br />

graph <strong>is</strong> in the RED the operator must glance at the appliances and shut off or turn down<br />

any that are not in use. If all the appliances are being used to cook products then the<br />

operation <strong>is</strong> profitable. The equipment <strong>is</strong> being properly utilized for the operation and it<br />

<strong>is</strong> acceptable for the efficiency graph to be in the RED. “SEE YOUR SAVINGS” by<br />

using the graph.<br />

7. Optional Wireless Remote<br />

1. The standard <strong>TRUFLOW</strong> system can be supplied with a wireless remote to<br />

provide a remote override button from another location in the kitchen.<br />

2. Truflow panel Kitchen One <strong>is</strong> on:<br />

a) Press the wireless remote once and the exhaust immediately<br />

ramps to 100% for approximately 15 minutes.<br />

b) Press the wireless remote again and hold for two (2) seconds<br />

the exhaust returns to normal operation.<br />

3. Truflow panel Kitchen One <strong>is</strong> off:<br />

c) Press the wireless remote once and the exhaust immediately<br />

ramps to 100% for approximately 15 minutes.<br />

d) Press the wireless remote again and hold for two (2) seconds and the exhaust<br />

and supply return to normal operation.<br />

e) Press the wireless remote again and hold for four (4) seconds and the exhaust<br />

and supply shut off.<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 24


APPENDIX A.<br />

Minimum duct velocity in the Building Code<br />

The National Fire Protection Association code, NFPA-96 2001, changed to provide for a<br />

reduction of the exhaust air from a commercial kitchen during low demand periods. The<br />

minimum duct velocity in the NFPA-96 2001 has been reduced from 1500 fpm to 500<br />

fpm. In addition the International Building Code, IBC, was changed in 2003 to allow for<br />

the reduction in exhaust from a commercial kitchen during low demand periods. Local<br />

building and fire departments have these codes in their possession and will have no<br />

reason not to allow a <strong>TRUFLOW</strong> installation anywhere in North America.<br />

International Mechanical Code. 2003<br />

Section 507 Commercial Kitchen Hoods<br />

507.1 General<br />

Exceptions:<br />

3. Net exhaust volumes for hoods shall be permitted<br />

to be reduced during no-load cooking conditions,<br />

where engineered or l<strong>is</strong>ted multi-speed or variablespeed<br />

controls automatically operate the exhaust<br />

system to maintain capture and removal of cooking<br />

effluents as required by th<strong>is</strong> section.<br />

NFPA-96, 2001<br />

8.2 <strong>Air</strong>flow<br />

8.2.1 <strong>Air</strong> Velocity<br />

8.2.1.1 The air velocity through any duct shall be<br />

not less than 152.1m/min (500 ft/min)<br />

Sizing the Exhaust Ductwork<br />

We recommend that the engineer size the exhaust ductwork for 1670 fpm velocity. The<br />

NPFA-96 code allows for a reduction in duct velocity to 500 fpm. By sizing the<br />

ductwork at 1670 for 100%, exhaust and duct velocity will be 500 fpm at 30% exhaust<br />

volume.<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 25


APPENDIX B.<br />

<strong>TRUFLOW</strong> Panel Model Number<br />

RPD-P 1 1 A W 2 TF 1 SC<br />

1- Total number of exhaust fan (Up to five exhaust fans)<br />

1- Total number of supply fans (one per kitchen)<br />

A- Standard Panel<br />

B- BACnet or LON panel.<br />

W- Wall mounted panel<br />

H – Hood mounted panel<br />

2- Total number of kitchens<br />

TF- <strong>TRUFLOW</strong> Variable Speed<br />

1- Total number of exhaust hood duct collars (10 per kitchen)<br />

SC- Supply 4-20 milliamps<br />

SV- Supply VSD<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 26


APPENDIX C.<br />

Truflow stainless steel enclosures dimensions<br />

Hood mounted.<br />

<strong>TRUFLOW</strong> enclosure, hood mounted<br />

Figure 45<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 27


APPENDIX D.<br />

Truflow stainless steel enclosures dimensions<br />

Wall Mounted.<br />

<strong>TRUFLOW</strong> enclosure wall mounted<br />

Figure 46<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 28


APPENDIX E.<br />

Remote Wiring<br />

<strong>TRUFLOW</strong> Control panel wiring schematic One Kitchen<br />

Figure 47<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 29


<strong>TRUFLOW</strong> Control panel wiring schematic Two Kitchens<br />

Figure 48<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 30


<strong>TRUFLOW</strong> Control panel wiring schematic Three Kitchens<br />

Figure 49<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 31


<strong>TRUFLOW</strong> Control panel wiring schematic Four Kitchens<br />

Figure 50<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 32


APPENDIX F.<br />

Sample Specification<br />

The commercial kitchen energy management controller shall be a <strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> TruFlow-<br />

EMC model RPD-PXX-AH-TF-X-WV. The Truflow shall provide semi automatic variable speed<br />

operation 24 hour/day for the commercial kitchen ventilation system. The panel shall be CSA<br />

certified and supplied in an 18GA stainless steel enclosure with No. 4 fin<strong>is</strong>h for hood, surface<br />

wall, or recessed wall mounting. The Truflow NEMA4x Touchscreen operates in conjunction with<br />

an integral PLC to provide daily reduction of the commercial kitchen exhaust and supply, and<br />

real-time temperature based control of energy target goal management. Truflow has optional<br />

LON, BACnet or MODbus interfaces to the Building Automation <strong>Systems</strong> (BAS). Each Truflow<br />

panel shall be internet accessible with a secure password through the local IP address for each<br />

location. The internet operator shall access the Touchscreen panel and view, control, or execute<br />

all functions available to the local kitchen operator.<br />

The Touchscreen controller shall be complete with Dashboard, System Control, Alarm Status,<br />

Reports and Setup & Diagnostic screens.<br />

The Dashboard screen shall graph energy usage throughout the day measuring energy<br />

consumption against user-set goals. The Dashboard screen also d<strong>is</strong>plays exhaust volume,<br />

outdoor temperature, hood lights, and % of goal reduction that <strong>is</strong> achieved each minute of the<br />

day.<br />

The System Control screen d<strong>is</strong>plays all components of the kitchen ventilation system: hood<br />

lights, fan on/off, summer/winter switch, and overrides. Each Truflow <strong>is</strong> capable of providing five<br />

independent systems with a maximum of five exhaust variable speed drives and one supply<br />

variable speed drive and/or a 4-20 milliamp output for each system.<br />

The Alarm Status Screen indicates and logs all alarm events which include: high temperature<br />

operation, electrical faults, J-couple faults, and supply drive communication error/failure and<br />

exhaust/supply drive communication error/failure.<br />

The Report screen provides fingertip selection of reports for Year to Date cost of gas, Year to<br />

Date cost of electricity, Daily cost of Utilities, % time exceeding goal and % time in override.<br />

The System Setup screen <strong>is</strong> accessible by the admin<strong>is</strong>trator with a secure password to customize<br />

the screen to the user, enter reduction goal, operating times, utility costs and provides system<br />

diagnostics.<br />

The Truflow modulates the exhaust and supply volume through variable speed exhaust and<br />

supply motor drives and/or a 4-20 milliamp output. The commercial kitchen ventilation system<br />

modulates from 30 to 100% to provide necessary exhaust during kitchen operation. When the<br />

mushroom pushbutton located under the panel <strong>is</strong> activated manually the exhaust volume will<br />

automatically increase to 100% for 15 minutes. After 15 minutes the system automatically reverts<br />

back to temperature based control. The 15 minutes <strong>is</strong> adjustable at the controller. The panel <strong>is</strong><br />

supplied with a room and outdoor temperature transducer.<br />

Options:<br />

• The panel <strong>is</strong> hood mounted or wall mounted<br />

• The panel does not/does include optional drive enclosure<br />

• There are a maximum of 5 systems (kitchens) to be controlled, with up to 5 exhaust fans<br />

and one supply fan per system (kitchen) and 10 hoods per kitchen<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 33


Remote Wiring Connections:<br />

Wiring to panel:<br />

• Power supply to the RPD-PXX-AH-TF-X-WV 15 amps 120V/1/60<br />

• Interlock from Building Automation System (BAS), CAT5 cable<br />

• Internet connection<br />

Wiring Drives:<br />

• High voltage power supply from breaker panel to input side of each drive<br />

• High voltage power wiring from output side of each drive to fan mounted motor<br />

d<strong>is</strong>connect switch<br />

Wiring from panel:<br />

• Interlock each drive with CAT5 connection in parallel<br />

• CAT5 cable to Outdoor temperature transducer located in a fresh air inlet<br />

Remote Wiring:<br />

• Power supply to the RPD-PXX-AH-TF-X-WV at 15 amps 120V/1/60<br />

• Power supply XXXV/3/60 from breaker panel to variable speed exhaust fan drive(s)<br />

• Power supply XXXV/3/60 from breaker panel to variable speed supply fan drive(s)<br />

• Power supply from the variable speed supply fan drive to the supply fan d<strong>is</strong>connect switch<br />

• Power from the variable speed exhaust fan drive(s) to the exhaust fan d<strong>is</strong>connect switch<br />

• Interlock to shunt trip 120V/1/60 – 2 amps maximum<br />

• Interlock to fire suppression system 120V/1/60 – 2 amps maximum<br />

• Interlock two (2) thermocouple wires from controller to each duct collar. Thermocouple wire <strong>is</strong><br />

supplied by <strong>Spring</strong> <strong>Air</strong><br />

• Interlock two (2) wires 4-20 milliamp signal to supply fan variable speed drive<br />

<strong>Spring</strong> <strong>Air</strong> <strong>Systems</strong> <strong>TRUFLOW</strong> Engineering Manual December 2007 34


Other Fine Products From<br />

SPRING AIR SYSTEMS...<br />

• Water Wash Ventilators<br />

♦ Hot Water Wash<br />

♦ Cold Water Spray/Hot Water Wash<br />

♦ Water Wash Control Panels<br />

• Dry Extractor Hoods<br />

• Revlow Hoods<br />

• Cartridge Hoods<br />

• Filter Hoods<br />

• Surface Fire Suppression<br />

• Commercial Kitchen Exhaust Fans<br />

• Kitchen Enviro <strong>Systems</strong><br />

♦ KES - 100% Exhaust<br />

• Commercial Kitchen Supply Units<br />

• Compensating Hoods<br />

• Exhaust Fans<br />

• Supply Fans<br />

• Commercial Kitchen Control Panels<br />

• Truflo & Melink Variable Speed Exhaust/Supply <strong>Systems</strong><br />

• Utility D<strong>is</strong>tributions <strong>Systems</strong><br />

Phone: 905-338-2999, FAX: 905-338-1079, e-mail info@springairsystems.com<br />

www.springairsystems.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!