Dual <strong>fuel</strong> burner selection<br />

Model RGL50, 1LN version<br />

[“WC] Burner model RGL50/1-B, vers. ZM-1LN<br />

Combustion head G40/2-LN 217x35K<br />

MBH Natural gas 1,<strong>70</strong>0 – 11,600<br />

Propane 1,<strong>70</strong>0 – 11,600<br />

GPH Light oil #2 20 – 82<br />

Combustion head “open”<br />

Combustion head “closed”<br />

[“WC ] Burner model RGL50/2-A, vers. ZM-1LN<br />

Combustion head G50/2-LN 260x40<br />

MBH Natural Gas 2,050 – 16,7<strong>30</strong><br />

Propane 2,7<strong>30</strong> – 16,7<strong>30</strong><br />

GPH Light oil #2 21 – 120<br />

Combustion head “open”<br />

Combustion head “closed”<br />

8<br />

7<br />

6<br />

5<br />

4<br />

3<br />

2<br />

1<br />

0<br />

Nat gas/LPG<br />

Light oil<br />

-1<br />

[MBH] 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000<br />

8<br />

7<br />

6<br />

5<br />

4<br />

3<br />

2<br />

1<br />

0<br />

Nat gas<br />

Propane<br />

Light oil<br />

Light oil<br />

-1<br />

[MBH] 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000<br />

[GPH] 0 10 20 <strong>30</strong> 40 50 60 <strong>70</strong> 80 90<br />

[GPH] 0 20 40 60 80 100 120<br />

Burner model Version<br />

RGL50/1-B ZM-1LN<br />

RGL50/2-A ZM-1LN<br />

The ratings given are based on <strong>fuel</strong> with low calorific value<br />

and an installation altitude of 0 ft. (0 m). Depending on the<br />

altitude of the installation, a reduction in capacity of<br />

approximately 1% for every 328 ft. (100 m) above sea level<br />

should be taken in<strong>to</strong> account.<br />

The stated oil throughputs are based on a calorific value of<br />

140,000 BTU/Gal for light oil<br />

Voltages and frequencies:<br />

As standard, the <strong>burners</strong> are suitable for three phase alternating<br />

current available with various voltages from 208 - 600V, 60Hz.<br />

Different voltages and frequency are available on request.<br />

Standard burner mo<strong>to</strong>r:<br />