Weishaupt dual fuel burners Sizes 30 to 70 ... - Pamber Energy
Weishaupt dual fuel burners Sizes 30 to 70 ... - Pamber Energy
Weishaupt dual fuel burners Sizes 30 to 70 ... - Pamber Energy
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Dual <strong>fuel</strong> burner selection<br />
Model RGL50, 1LN version<br />
[“WC] Burner model RGL50/1-B, vers. ZM-1LN<br />
Combustion head G40/2-LN 217x35K<br />
MBH Natural gas 1,<strong>70</strong>0 – 11,600<br />
Propane 1,<strong>70</strong>0 – 11,600<br />
GPH Light oil #2 20 – 82<br />
Combustion head “open”<br />
Combustion head “closed”<br />
[“WC ] Burner model RGL50/2-A, vers. ZM-1LN<br />
Combustion head G50/2-LN 260x40<br />
MBH Natural Gas 2,050 – 16,7<strong>30</strong><br />
Propane 2,7<strong>30</strong> – 16,7<strong>30</strong><br />
GPH Light oil #2 21 – 120<br />
Combustion head “open”<br />
Combustion head “closed”<br />
8<br />
7<br />
6<br />
5<br />
4<br />
3<br />
2<br />
1<br />
0<br />
Nat gas/LPG<br />
Light oil<br />
-1<br />
[MBH] 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000<br />
8<br />
7<br />
6<br />
5<br />
4<br />
3<br />
2<br />
1<br />
0<br />
Nat gas<br />
Propane<br />
Light oil<br />
Light oil<br />
-1<br />
[MBH] 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000<br />
[GPH] 0 10 20 <strong>30</strong> 40 50 60 <strong>70</strong> 80 90<br />
[GPH] 0 20 40 60 80 100 120<br />
Burner model Version<br />
RGL50/1-B ZM-1LN<br />
RGL50/2-A ZM-1LN<br />
The ratings given are based on <strong>fuel</strong> with low calorific value<br />
and an installation altitude of 0 ft. (0 m). Depending on the<br />
altitude of the installation, a reduction in capacity of<br />
approximately 1% for every 328 ft. (100 m) above sea level<br />
should be taken in<strong>to</strong> account.<br />
The stated oil throughputs are based on a calorific value of<br />
140,000 BTU/Gal for light oil<br />
Voltages and frequencies:<br />
As standard, the <strong>burners</strong> are suitable for three phase alternating<br />
current available with various voltages from 208 - 600V, 60Hz.<br />
Different voltages and frequency are available on request.<br />
Standard burner mo<strong>to</strong>r:<br />
Isolation class F, IP 54 protection<br />
10