Dual <strong>fuel</strong> burner selection<br />
Models GL and RGL<strong>30</strong>, 1LN version<br />
[“WC ] Burner model GL<strong>30</strong>/2-A, vers. ZM-1LN<br />
GL<strong>30</strong>/2-A, vers. TM-1LN<br />
RGL<strong>30</strong>/2-A, vers. ZM-1LN<br />
Combustion head<br />
G<strong>30</strong>/2-LN 190x35<br />
MBH Nat. Gas/Propane 1,000 – 6,400<br />
GPH Light oil #2 9 – 45<br />
5<br />
Combustion head “open”<br />
Combustion head “closed”<br />
4<br />
3<br />
2<br />
1<br />
0<br />
Nat gas/LPG<br />
Light oil<br />
Light oil<br />
-1<br />
[MBH] 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000<br />
[GPH] 0 10 20 <strong>30</strong> 40 50<br />
Burner model Version<br />
GL<strong>30</strong>/2-A ZM-1LN<br />
GL<strong>30</strong>/2-A TM-1LN<br />
The ratings given are based on <strong>fuel</strong> with low calorific value<br />
and an installation altitude of 0 ft. (0 m). Depending on the<br />
altitude of the installation, a reduction in capacity of<br />
approximately 1% for every 328 ft. (100 m) above sea level<br />
should be taken in<strong>to</strong> account.<br />
RGL<strong>30</strong>/2-A<br />
ZM-1LN<br />
The stated oil throughputs are based on a calorific value of<br />
140,000 BTU/Gal for light oil<br />
Voltages and frequencies:<br />
As standard, the <strong>burners</strong> are suitable for three phase alternating<br />
current available with various voltages from 208 - 600V, 60Hz.<br />
Different voltages and frequency are available on request.<br />
Standard burner mo<strong>to</strong>r:<br />
Isolation class F, IP 54 protection<br />