Winter-time ventilation strategy.<br />

1 = Dampers at the intake, 2 = dampers and heating elements at the perimeter of the<br />

light well base, 3 = fully glazed light well base, 4 = light well fills with warmed air, 5 =<br />

air enters each floor through a bottom-hung opening window across a secondary heat<br />

source, 6 = acoustically treated transfer ducts in deep partitions at high and low levels,<br />

7 = first and second floor exits coupled, 8 = third and fourth floor exits coupled, 9 = fifth<br />

floor dedicated vent stack, 10 = street-side spaces exhaust into the stair hall, double<br />

façade, 11 = stair hall exhaust via the ‘breathing parapet’, 12 = third floor dedicated<br />

exhaust, 13 = fourth floor dedicated exhaust, 14 = lower ground floor is exhausted by<br />

a dedicated full height stack