Fig. 8 – Trace of internal & external temperatures – typical floor (2 nd )<br />

As commissioning and fine tuning continue a better performance is evident. Internal<br />

temperatures are up to 10 degrees lower than external temperatures. The<br />

commissioning has highlighted that the air flows throughout the building are at least<br />

as complex as suggested by the BP Institute.<br />

1. Stability of internal temperature against external. Internal conditions fluctuate<br />

approx. 2 degrees against approx. 16 degrees externally, 2. Effect of night cooling<br />

the exposed internal structure – typically depressing the temperature by 2 degrees<br />

for the start of the next day, 3. Typically 1 degree variation between front and back<br />

sections of building, 4. Internal temperatures are depressed up to 10 degrees<br />

during daytime.