5 Modbus RTU VLT ® Micro Drive FC 51 Operating Instructions<br />

Response<br />

The normal response is an echo of the query, returned after the register contents have been passed.<br />

Field Name<br />

Example (HEX)<br />

Slave address 01<br />

Function 06<br />

Starting Address HI 00<br />

Starting Address LO<br />

1D<br />

No. of Points HI 00<br />

No. of Points LO 01<br />

Error Check (CRC) -<br />

Table 5.1: Normal response frame<br />

5<br />

5.5.6 Preset Multiple Registers (10HEX)<br />

Description<br />

This function presets a value into a sequence of holding registers.<br />

Query<br />

The query message specifies the register references to be preset. Register addresses start at zero, i.e. register 1 is addressed as 0.<br />

Example<br />

Write 65535 (655.35s) to PNU734 (4-bytes) mapped to 0 x 1CAB<br />

Field Name<br />

Example (HEX)<br />

Slave address 01<br />

Function 10<br />

Starting Address HI<br />

1C<br />

Starting Address LO<br />

AB<br />

No. of Registers HI 00<br />

No. of Registers LO 02<br />

Byte count 04<br />

Write Data HI (Register 7339) 00<br />

Write Data LO (Register 7339) 00<br />

Write Data HI (Register 7340)<br />

FF<br />

Write Data LO (Register 7340)<br />

FF<br />

Error Check (CRC) -<br />

Table 5.1: Request frame<br />

Response<br />

The normal response returns the slave address, function code, starting address, and quantity of registers preset.<br />

Field Name<br />

Example (HEX)<br />

Slave address 01<br />

Function 10<br />

Starting Address HI<br />

1C<br />

Starting Address LO<br />

AB<br />

No. of Registers HI 00<br />

No. of Registers LO 02<br />

Error Check (CRC) -<br />

Table 5.1: Normal response frame<br />

34 MG.02.A4.02 - VLT ® is a registered Danfoss trademark