28.11.2014 Views

Ferraz - Efo-power.ru

Ferraz - Efo-power.ru

Ferraz - Efo-power.ru

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Semiconductor (A) fuses<br />

Semiconductor (AC) fuses<br />

American Round Fuses<br />

Form 101 Range<br />

A100P<br />

Semiconductor Protection Fuses<br />

I 2 t Data – 1000 Volts AC, 100kA<br />

1000 VAC Fault<br />

Load<br />

Ampere<br />

Rating<br />

Melting<br />

(A 2 x10 3 )<br />

I 2 t Data<br />

Clearing<br />

@1000VAC (fig A)<br />

(A 2 x10 3 )<br />

15 .023 .6<br />

20 .03 .8<br />

25 .047 1.3<br />

30 .057 1.5<br />

35 .29 2.2<br />

40 .38 2.9<br />

50 .60 4.5<br />

60 .86 6.5<br />

65 1.0 7.6<br />

70 1.2 8.8<br />

80 1.5 12<br />

100 2.4 18<br />

125 3.8 28<br />

150 5.4 41<br />

200 9.6 72<br />

225 12 91<br />

250 15 110<br />

300 22 160<br />

350 29 220<br />

400 38 290<br />

500 600 450<br />

600 86 650<br />

650 100 760<br />

700 120 880<br />

800 150 1,200<br />

1,000 240 1,900<br />

CORRECTION FACTOR FOR I2T<br />

Fig. A<br />

Clearing I 2 t vs. AC<br />

Operating Voltage<br />

OPERATING VOLTAGE (AC RMS VOLTS)<br />

Watts Loss at Rated Current<br />

Watts Loss vs. % Rated Current<br />

Ampere<br />

Rating<br />

Watts<br />

Loss (W)<br />

Ampere<br />

Rating<br />

Watts<br />

Loss (W)<br />

15 3.4 225 40<br />

20 5.9 250 45<br />

25 9 300 55<br />

30 12.8 350 65<br />

35 7.3 400 70<br />

40 8.3 500 90<br />

50 11 600 110<br />

60 13 650 120<br />

70 13 700 125<br />

80 14 800 140<br />

100 18 1000 190<br />

125 23<br />

150 28<br />

200 36<br />

CORRECTION FACTOR FOR WATTS LOSS<br />

PERCENT RATED CURRENT<br />

12/04<br />

SCAC39

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!