Chapter 3<br />
Structured Cable Field Calibration and Testing<br />
3-4<br />
GG45 – TROUBLESHOOTING<br />
A field calibration should be performed prior to implementing a test of the GG45<br />
cabling system. This process will ensure (1) synchronizing of the units, (2) qualifying<br />
(testing) of the patchcords and (3) gathering of loss data regarding the patchcords<br />
and mated connections.<br />
The equipment required for a GG45 calibration procedure is:<br />
� Display Handset<br />
� Remote Handset<br />
� GG45 Calibration Adapters<br />
(Two adapters joined by a short segment of Category 7 cable)<br />
� GG45 Calibration Load Terminator (100Ω Jack)<br />
� GG45 Permanent Link Adapters<br />
(A set of two adapters, each with a patchcord (approximately 2 meters) soldered<br />
to the adapter at one end and a GG45 Category 7 plug at the opposite end)<br />
TESTING A GG45 CABLING SYSTEM<br />
Figure 3-1: Typical Configuration for GG45 Cable Testing<br />
Typical configuration for testing has the DH unit and RH unit connected to the GG45<br />
Permanent Link Adapters. The cable under test is connected at the Category 7 plug<br />
end of both the DH and RH ends.