02.01.2015 Views

View Bid - Loudoun Water

View Bid - Loudoun Water

View Bid - Loudoun Water

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Loudoun</strong> <strong>Water</strong> May 28, 2013<br />

3.6.2.2.1.3. Lot or stockpile number<br />

identification<br />

3.6.2.3. Vendor’s certification of installation, signed by Vendor’s<br />

representative, certifying that product was installed<br />

according to manufacturer’s recommendations.<br />

4. SPECIFIC PROJECT REQUIREMENTS<br />

4.1. General<br />

4.1.1. The GAC shall be capable of removing COD from membrane<br />

permeate (MP). The GAC shall be made from selected grades of<br />

bituminous coal capable of withstanding repeated backwash<br />

procedures without significant change in physical sizes and shall<br />

be suitable for thermal reactivation and re-use. Only coal-based<br />

GAC will be acceptable.<br />

4.2. Manufacturers and Products<br />

4.2.1. GAC shall be:<br />

4.2.1.1. Filtrasorb 300 by Calgon Carbon Corporation.<br />

4.2.1.2. GAC300 by Norit Americas, Inc.<br />

4.2.1.3. Westates – UltraCarb 830 by Siemens<br />

4.2.2. No substitutes allowed.<br />

4.3. Manufacturer’s Qualifications<br />

4.3.1. Manufacturers shall have a minimum of fifteen (15) years<br />

experience manufacturing coal-based GAC for municipal water<br />

and wastewater treatment applications and shall submit proof in<br />

the form of a Manufacturer’s Certificate and/or Affidavit of<br />

Compliance.<br />

4.3.2. Manufacturer shall certify that it is the owner and operator of a<br />

reactivation facility.<br />

4.3.3. Manufacturer must certify the source of coal, the carbon<br />

manufacturing location, and the agglomeration/thermal process.<br />

4.4. Service Conditions<br />

4.4.1. Number of Contactors: 6<br />

4.4.2. Number of Cells per Contactor: 2<br />

4.4.3. Surface Area per Cell: 403 ft 2<br />

4.4.4. Volume GAC per Cell - Bed depth of 11 feet: 4,443 ft 3<br />

4.4.5. Working Temperature: 45 to 75 degrees F<br />

4.4.6. Working pH: 6 to 8<br />

4.4.7. Working Pressure: 0 to 15 psig<br />

4.5. Product Specifications<br />

4.5.1. The GAC shall be procured from coal mined in North America.<br />

Granular Activated Carbon<br />

For BRWRF 4 IFB No. 2013-011-240