ARGUS PRESENCE DETECTOR.<br />

Save energy with system.<br />

ARGUS Presence – the functional<br />

principle<br />

Installed on the ceiling of a room, the<br />

ARGUS presence detector detects<br />

the presence of persons in a range<br />

of Ø 8 m (if installed at a height of<br />

2.50 m) and simultaneously measures<br />

the intensity of the natural light. If the<br />

ambient light drops below a predefined<br />

threshold, the slightest movements in<br />

the room will automatically activate the<br />

lighting via the first channel. However,<br />

if there is enough ambient light or the<br />

ARGUS no longer detects a presence,<br />

the presence detector will switch the<br />

light off again, thus saving costs. The<br />

second channel controls all the<br />

systems connected to it, such as heating,<br />

ventilation or alarm systems, independently<br />

of the first channel. Thus,<br />

for example, the ventilation/heating will<br />

stay on while the light is switched off<br />

due to adequate outside brightness.<br />

ARGUS Presence Detector System<br />

For complete monitoring of large rooms<br />

or long corridors. Up to 8 sensor heads<br />

can be switched in series. This makes<br />

it possible to monitor corridors up to<br />

64 m long and control them in a<br />

targeted way. For use in open-plan<br />

offices, it is possible to combine pushbuttons<br />

for manual operation of the<br />

lighting via an extension input.<br />

<strong>IN</strong>STABUS ARGUS presence detector<br />

The functions of the 2 switching channels<br />

Channel 1<br />

Brightness-dependent and high level of<br />

sensitivity.<br />

Switches the light on if there is<br />

inadequate brightness.<br />

Learns independently at what level of<br />

brightness the light can be switched off<br />

despite continuous movements.<br />

Brightness sensor infinitely adjustable<br />

from 10 – 1000 Lux.<br />

ON time infinitely adjustable<br />

from 10 s – 30 min.<br />

Channel 2<br />

Brightness-independent.<br />

Only several movements within a<br />

period of time lead to the light being<br />

switched on.<br />

ON times infinitely adjustable<br />

from 5 min – 2 h.<br />

Suitable for controlling heating or fan<br />

motors.<br />

A combination with <strong>IN</strong>STABUS EIB<br />

offers further options for a modern<br />

building management system, in addition<br />

to the economic and environmental<br />

benefit offered by the ARGUS<br />

Presence: e.g. notification of faults and<br />

system statuses, safety monitoring,<br />

control of blinds as well as the central<br />

control of all building functions. The<br />

version with IR receiver, for example,<br />

allows up to 10 channels to be controlled<br />

via remote control (6x switching/<br />

dimming and 2x blinds). Or <strong>IN</strong>STABUS<br />

ARGUS Presence with constant light<br />

adjustment: light-dependent constant<br />

light adjustment is possible by means<br />

of an integrated brightness sensor.<br />

Surface-mounted housing<br />

Thanks to the surface-mounted housing,<br />

ARGUS presence detectors can<br />

also be mounted on the surface.<br />

The surveillance range depends on the installation height. The table shows the<br />

surveillance range for different installation heights.<br />

Installation height (m)<br />

2.0<br />

2.5<br />

3.0<br />

3.5<br />

4.0<br />

The detection sensitivity is reduced<br />

with an installation height of over<br />

3 metres. Larger movements will then<br />

be necessary to trigger a switching<br />

event.<br />

Surveillance range (m 2 )<br />

33<br />

50<br />

70<br />

95<br />

133<br />

If the ARGUS Presence is installed<br />

higher than 4 metres, then only walking<br />

persons will be detected. This is a<br />

possibility for storerooms or sport halls,<br />

for example.<br />