06.01.2015 Views

Catalog - Tri-State Technical Sales Corp.

Catalog - Tri-State Technical Sales Corp.

Catalog - Tri-State Technical Sales Corp.

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

ACCESSORIES AND OPTIONS<br />

Backflow Preventer (Standard Feature)<br />

If outlet pressure exceeds the inlet pressure, the main valve can<br />

open and backfow may occur. To prevent backflow, a standard<br />

backflow preventer is incorporated in the F200, F300, and<br />

F500 pilots. An increase in the outlet pressure above the inlet is<br />

transmitted to the top of the main valve piston, thus keeping<br />

the main valve closed and protecting the vessel from exposure<br />

to backpressure and backflow contamination.<br />

DOME<br />

COMMUNICATION<br />

PORT<br />

INLET FEED<br />

EXHAUST<br />

BACKPRESSURE<br />

INLET<br />

14<br />

CLOSED WITH BACKPRESSURE<br />

GREATER THAN INLET PRESSURE<br />

INLET<br />

CLOSED WITH INLET PRESSURE APPLIED<br />

Manual/Remote Blowdown<br />

This allows the main valve to lift without opening the pilot valve,<br />

by discharging the piston dome pressure directly to the<br />

atmosphere. This is accomplished by use of a manual or<br />

automatic blowdown valve, e.g. hand valve or solenoid valve.<br />

MANUAL<br />

VALVE<br />

F7000/8000 SERIES