SIZING AND SET PRESSURE CONSIDERATIONS FOR BACKPRESSURE<br />

18<br />

Constant Backpr essur e Sizing Factor (K b<br />

)<br />

(Gases & V apors Only)<br />

In general, backpr essur e has no ef fect on the flow<br />

capacity of the FLOW SAFE F7000/8000 Series of pilo t-<br />

operated valves as long as a critical flow condition exists.<br />

The critical flow pr essur e ratio for a particular gas may be<br />

estimated per API RP 520 by the equation below:<br />

P cf<br />

[<br />

2<br />

]<br />

=<br />

P 1<br />

K + 1<br />

k /(k-1)<br />

k = Specific heat ratio for gas, C p /C v<br />

(see page 20)<br />

P 1<br />

= Upstr eam relieving pr essur e (psia)<br />

P cf<br />

= Critical flow nozzle pr essur e (psia)<br />

P B<br />

= Backpr essur e, psi a<br />

P s<br />

= Set pr essur e, psi a<br />

P o<br />

= O verpr essur e, psi<br />

W hen suf ficient back pr essur e exists to cr eate<br />

a subcritical flow condition, the critical sizing equatio n<br />

shown on Page 16 should be used along with the Backpr<br />

essur e Sizing Factor (K b<br />

) shown in the chart below .<br />

This method is described in detail in API RP520.<br />

Set pr essur es ar e not af f ected by backpr essur e when<br />

using the F300 or F500 pilot valve as it is balanced against<br />

such pr essur e, or the F200 as it is normally vented to<br />

atmosphe re . Caution should be used if the F200 vent is<br />

r outed to the main valve discharge or other pr essurized<br />

vessel, as the set pr essur e and blowdown may be<br />

af fected.<br />

Backpr essur e gr eater than the system inlet pr essur e<br />

normally would cause the main valve piston to open.<br />

Because the F200, F300, and F500 pilot valves ar e equipped<br />

w ith backflow pr eventers as standar d featur es, this<br />

cannot occur on the F7000/8000 valves. The<br />

backpr essur e is r outed to the main valve piston<br />

dome, keeping the valve closed and bubble-tight .<br />

Example: See figur e below .<br />

S et Pr essur e = 100 psig<br />

Overpr essur e = 10 psi<br />

Superimposed backpr essur e = 70 psi g<br />

Built-up backpr essur e = 10 ps ig<br />

Per cent absolute<br />

backpressure =<br />

K b<br />

= 0.87(for k=1.4)<br />

70+10+14. 7<br />

100+10+14. 7<br />

x 100 = 76%<br />

F7000/8000 SERIES