MAXIM 3 ® WATER HEATER<br />

13 TROUBLESHOOTING GUIDE<br />

Problem Probable Cause Corrective Action<br />

Starting or Pre-purge<br />

Failure<br />

Flame Failure<br />

Power Supply<br />

On-Off Switch<br />

Temperature Control<br />

Flame Safeguard Control<br />

Remote enable/disable open<br />

Combustion Air blower<br />

Air-proving Switch<br />

Blocked Filter Switch<br />

Flame Control Pressure Switch<br />

Loose Wire Connections<br />

Power Supply<br />

Flame Safeguard Control<br />

Hot Surface Igniter<br />

Air-proving Switch<br />

Gas Pressure<br />

Combustion<br />

Grounding<br />

Safety Limits<br />

Check fuse and/or circuit breaker. Check voltage at<br />

120/24V step-down transformer.<br />

Check if On-Off switch is lighted<br />

Check that the operating temperature control is set<br />

higher than the temperature of the water heater.<br />

Check for bad ground or bad control. Replace if<br />

necessary.<br />

Enable water heater or place jumper between<br />

terminals R1-R2.<br />

Check if fan connection terminals on flame control<br />

is closed<br />

Check for 24V at field access terminal C2. Remote<br />

interlock may be open.<br />

Fan VFD may be defective. Verify proper voltage.<br />

Check switch contacts are closed.<br />

Check for 24V at the N.O. side of air switch<br />

Check for 24V at the <strong>com</strong>mon side of air switch<br />

Check for proper blower pressure setting – adjust if<br />

required. Air switch may be defective.<br />

Check for 24V at the N.C. side of the blocked filter<br />

switch. Replace filter or switch as required.<br />

Check for 24V at the pressure switch terminal.<br />

Check connections to all <strong>com</strong>ponents<br />

Check fuse and/or circuit breaker. Check voltage at<br />

120/24V step-down transformer.<br />

Check for bad ground or bad control. Replace if<br />

necessary.<br />

Check resistance at room temperature and then the<br />

amperage draw during heat-up. Replace if the<br />

measured amperage is not within 3.5 to 5.0 Amps<br />

or if measured resistance is not within 40-100 ohms<br />

(at room temperature). Also, check for overheating<br />

condition due to damaged refractory around igniter.<br />

Check if switch is bouncing. Adjust or replace.<br />

Check for proper inlet static and dynamic gas<br />

pressure.<br />

Inadequate flame signal may result from improper<br />

<strong>com</strong>bustion. Adjust to proper CO2 levels at low fire.<br />

Check for proper ground from flame control to<br />

burner housing.<br />

Check all safety limits for fault condition and correct<br />

as required.<br />

28<br />

PV500-51 03/14