MAXIM 3 ® WATER HEATER<br />
13 TROUBLESHOOTING GUIDE<br />
Problem Probable Cause Corrective Action<br />
Starting or Pre-purge<br />
Failure<br />
Flame Failure<br />
Power Supply<br />
On-Off Switch<br />
Temperature Control<br />
Flame Safeguard Control<br />
Remote enable/disable open<br />
Combustion Air blower<br />
Air-proving Switch<br />
Blocked Filter Switch<br />
Flame Control Pressure Switch<br />
Loose Wire Connections<br />
Power Supply<br />
Flame Safeguard Control<br />
Hot Surface Igniter<br />
Air-proving Switch<br />
Gas Pressure<br />
Combustion<br />
Grounding<br />
Safety Limits<br />
Check fuse and/or circuit breaker. Check voltage at<br />
120/24V step-down transformer.<br />
Check if On-Off switch is lighted<br />
Check that the operating temperature control is set<br />
higher than the temperature of the water heater.<br />
Check for bad ground or bad control. Replace if<br />
necessary.<br />
Enable water heater or place jumper between<br />
terminals R1-R2.<br />
Check if fan connection terminals on flame control<br />
is closed<br />
Check for 24V at field access terminal C2. Remote<br />
interlock may be open.<br />
Fan VFD may be defective. Verify proper voltage.<br />
Check switch contacts are closed.<br />
Check for 24V at the N.O. side of air switch<br />
Check for 24V at the <strong>com</strong>mon side of air switch<br />
Check for proper blower pressure setting – adjust if<br />
required. Air switch may be defective.<br />
Check for 24V at the N.C. side of the blocked filter<br />
switch. Replace filter or switch as required.<br />
Check for 24V at the pressure switch terminal.<br />
Check connections to all <strong>com</strong>ponents<br />
Check fuse and/or circuit breaker. Check voltage at<br />
120/24V step-down transformer.<br />
Check for bad ground or bad control. Replace if<br />
necessary.<br />
Check resistance at room temperature and then the<br />
amperage draw during heat-up. Replace if the<br />
measured amperage is not within 3.5 to 5.0 Amps<br />
or if measured resistance is not within 40-100 ohms<br />
(at room temperature). Also, check for overheating<br />
condition due to damaged refractory around igniter.<br />
Check if switch is bouncing. Adjust or replace.<br />
Check for proper inlet static and dynamic gas<br />
pressure.<br />
Inadequate flame signal may result from improper<br />
<strong>com</strong>bustion. Adjust to proper CO2 levels at low fire.<br />
Check for proper ground from flame control to<br />
burner housing.<br />
Check all safety limits for fault condition and correct<br />
as required.<br />