MAXIM 3 ® WATER HEATER<br />
3.5 Service Clearances<br />
Allow sufficient space to provide adequate clearances on all sides for service and inspection. At least 24” above the<br />
water heater is required for filter replacement and burner/gas control service, 18” at left and right sides of the<br />
appliance. Optional equipment may increase the clearance requirements. Allow sufficient space for installing and<br />
servicing connections such as water, gas, vent, <strong>com</strong>bustion air, electrical, pump and other auxiliary equipment.<br />
3.6 Clearances To Combustible Surfaces<br />
Minimum 1” clearance must be provided from any vent surface to adjacent <strong>com</strong>bustible material. The minimum<br />
clearances to unprotected <strong>com</strong>bustible material are 24” be provided at the front, 8” be provided at the rear and 8” at<br />
top, left and right sides of the appliance.<br />
4 GENERAL PIPING GUIDELINES<br />
4.1 Inlet and Outlet Connections<br />
1. Use only non-ferrous water piping and fittings. Do not use galvanized pipe or fittings. Use of ferrous or<br />
galvanized pipe or fittings can cause rust to form.<br />
2. Install shut-off valves and unions on the inlet and outlet water piping for servicing. Use caution when<br />
threading pipe nipples into tank connections to prevent cross threading, or over-tightening. Always use a<br />
back-up wrench on tank nipples when tightening unions, valves, etc.<br />
3. Insulate hot water and return circulation lines. Insulate cold water supply lines if subject to freezing during<br />
shutdown periods. IMPORTANT: Do not use the plumbing connected to the appliance as a ground for<br />
welding or any other purpose.<br />
4. Pipe the drain valve to a suitable open drain.<br />
4.2 Building Return Piping<br />
To <strong>maxim</strong>ize water heater efficiency, connect the building return (≈ 5 gpm) to the inlet piping as shown below.<br />
WATER HEATER PIPING GUIDELINE<br />
Single Water Heater – One Hot Outlet Temperature<br />
8<br />