Soft starters DS and DM - Moeller Electric Parts
Soft starters DS and DM - Moeller Electric Parts
Soft starters DS and DM - Moeller Electric Parts
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>DM</strong>4 soft <strong>starters</strong><br />
14/24<br />
Bypass circuit<br />
Engineering<br />
Connection examples<br />
After completion of the acceleration phase (full mains voltage reached), the soft<br />
starter M4 actuates the bypass contactor. This connects the motor directly with the<br />
mains.<br />
Actuation<br />
S2<br />
Q21 OK 33<br />
(no error)<br />
K1<br />
34<br />
L1<br />
L2<br />
L3<br />
N<br />
PE<br />
Q22<br />
S1<br />
Q21<br />
Q11<br />
F3<br />
M1<br />
K1<br />
K1<br />
S3<br />
13<br />
K1 Q22 S4 K2 K2 K1 Q21 RUN Q21 TOR<br />
14<br />
E2<br />
Q21 K2 Q21<br />
39<br />
1L1<br />
3L2<br />
5L3<br />
2T1<br />
4T2<br />
6T3<br />
M<br />
3~<br />
<strong>DM</strong>4<br />
a b<br />
Q1 Q1<br />
~ =<br />
E1<br />
Q11<br />
39<br />
I > I > I > I > I > I ><br />
F11<br />
b<br />
a<br />
⎧<br />
⎪<br />
⎨<br />
⎪<br />
⎩<br />
L N E1 E2 39<br />
0 V (E1;E2)<br />
K1;RUN K2;TOR K3 K4<br />
T1 T2 13 14 23 24 33 34 43<br />
0 V Analog<br />
7<br />
0 V Analog<br />
7<br />
+12 V DC<br />
~ =<br />
Imot<br />
+12 8<br />
REF 1: 0–10 V<br />
REF 2: 4–20 mA<br />
Analog Out 1<br />
Q22<br />
1<br />
Analog Out 2<br />
62 63<br />
c<br />
PE<br />
23<br />
24<br />
<strong>Moeller</strong> HPL0211-2007/2008<br />
http://catalog.moeller.net<br />
Advantage:<br />
• The soft starter’s heat dissipation is reduced to the heat dissipation at idle.<br />
• The limit values of radio interference class “B” are maintained.<br />
The bypass contactor is now switched into a zero-current state <strong>and</strong> can therefore be<br />
laid out to AC-1.<br />
If an EMERGENCY STOP requires an immediate isolation, the bypass contactor has<br />
to also switch the motor load <strong>and</strong> must therefore be laid out according to AC-3.<br />
EMERGENCY STOP<br />
S1: Off (unguided deceleration)<br />
S2: On<br />
a Enable<br />
b <strong>Soft</strong> start/soft stop<br />
a See actuation<br />
b Control voltage through Q1 <strong>and</strong> F11 or through Q2<br />
c Motor current indication<br />
E1: Start/stop<br />
E2: Enable<br />
T1: + Thermistor<br />
T2: … Thermistor<br />
For <strong>Moeller</strong> <strong>Electric</strong> Sales <strong>and</strong> Support call KMparts.com (866) 595-9616