<strong>DS</strong>4 soft <strong>starters</strong><br />

14/34<br />

Technical Data<br />

<strong>Soft</strong> <strong>starters</strong><br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

http://catalog.moeller.net<br />

<strong>DS</strong>4-340-7K5-MX(R) <strong>DS</strong>4-340-11K-MX(R) <strong>DS</strong>4-340-15K-MX(R)<br />

General<br />

St<strong>and</strong>ards IEC/EN 60947-4-2<br />

Approvals UL/CSA UL/CSA UL/CSA<br />

Climatic proofing Damp heat, constant according to IEC 60068-2-78; damp heat, cyclical, according to IEC 60068-2-10<br />

Ambient temperature °C 0 – 40 0 – 40 0 – 40<br />

Ambient temperature, storage °C 25…55 25…55 25…55<br />

Altitude m 0 – 1000 0 – 1000 0 – 1000<br />

Mounting position vertical vertical vertical<br />

Degree of protection (Power connection) IP21 IP21 IP21<br />

Protection against direct contact Finger <strong>and</strong> back-of-h<strong>and</strong> proof<br />

Overvoltage category/pollution degree II/2 II/2 II/2<br />

Shock resistance 8 g/11 ms 8 g/11 ms 8 g/11 ms<br />

Dimensions (W x H x D) mm 45 x 149 x 189.5 45 x 149 x 189.5 45 x 149 x 189.5<br />

Weight kg 0.8 0.8 1.6<br />

Radio interference level „A“ „A“ „A“<br />

Vibration resistance to EN 60721-3-2 2M2 2M2 2M2<br />

Average heat dissipation at rated load cycle W 11.2 11.9 12.7<br />

Main conducting paths<br />

Rated operating voltage Ue V AC 110 – 500 110 – 500 110 – 500<br />

Supply frequency Hz 50/60 50/60 50/60<br />

Control section power supply V AC internal via power connection<br />

Rated operational current<br />

AC-53 (inductive load) Ie A 16 23 31<br />

Assigned motor rating (st<strong>and</strong>ard connection)<br />

230 V kW 4 5.5 7.5<br />

400 V kW 7.5 11 15<br />

460 V HP 10 15 20<br />

500 V kW 7.5 11 18.5<br />

Overload cycle to IEC/EN 60947-4-2<br />

AC-53b (with bypass) 16A: AC-53b: 3 – 5; 360 23A: AC-53b: 3 – 5; 360 31A: AC-53b: 3 – 5; 360<br />

Terminal capacities<br />

Cable lengths<br />

Solid mm2 1 x (1.5 – 6)<br />

2 x (1.5 – 4)<br />

Flexible with ferrule mm2 1 x (1.5 – 6)<br />

2 x (1.5 – 2.5)<br />

Str<strong>and</strong>ed mm2 1 x (1.5 – 6)<br />

2 x (1.5 – 4)<br />

Solid or str<strong>and</strong>ed AWG 1 x (16 – 8)<br />

2 x (16 – 12)<br />

1 x (1.5 – 6)<br />

2 x (1.5 – 4)<br />

1 x (1.5 – 6)<br />

2 x (1.5 – 2.5)<br />

1 x (1.5 – 6)<br />

2 x (1.5 – 4)<br />

1 x (16 – 8)<br />

2 x (16 – 12)<br />

1 x (2.5 – 50)<br />

2 x (2.5 – 16)<br />

1 x (2.5 – 35)<br />

2 x (2.5 – 10)<br />

1 x (2.5 – 50)<br />

2 x (2.5 – 16)<br />

1 x (14 – 2)<br />

2 x (14 – 8)<br />

flat conductor<br />

Tightening torque Nm 1.7 1.7 3.5<br />

Screwdriver (PZ: Pozidriv) mm PZ2 or 1 x 6 mm PZ2 or 1 x 6 mm PZ2 or 1 x 6 mm<br />

Control cables<br />

Notes<br />

<strong>DS</strong>4<br />

Solid mm2 1 x (0.75 – 2.5)<br />

2 x (0.75 – 1.5)<br />

Flexible with ferrule mm2 1 x (0.75 – 2.5)<br />

2 x (0.75 – 1.5)<br />

Str<strong>and</strong>ed mm2 1 x (0.75 – 2.5)<br />

2 x (0.75 – 1.5)<br />

Solid or str<strong>and</strong>ed AWG 1 x (18 – 12)<br />

2 x (18 – 16)<br />

1 x (0.75 – 2.5)<br />

2 x (0.75 – 1.5)<br />

1 x (0.75 – 2.5)<br />

2 x (0.75 – 1.5)<br />

1 x (0.75 – 2.5)<br />

2 x (0.75 – 1.5)<br />

1 x (18 – 12)<br />

2 x (18 – 16)<br />

1 x (0.75 – 2.5)<br />

2 x (0.75 – 1.5)<br />

1 x (0.75 – 2.5)<br />

2 x (0.75 – 1.5)<br />

1 x (0.75 – 2.5)<br />

2 x (0.75 – 1.5)<br />

1 x (18 – 12)<br />

2 x (18 – 16)<br />

flat conductor<br />

Tightening torque Nm 0.8 0.8 0.8<br />

Screwdriver (PZ: Pozidriv) mm 0.5 x 3.5 0.5 x 3.5 0.5 x 3.5<br />

Rated impulse withst<strong>and</strong> voltage:<br />

•1.2 ms/50 ms (rise time/fall time of the pulse to IEC/EN 60947-2 or -3)<br />

• Applies for control circuit/power section/enclosure<br />

For <strong>Moeller</strong> <strong>Electric</strong> Sales <strong>and</strong> Support call KMparts.com (866) 595-9616