12.11.2012 Views

Soft starters DS and DM - Moeller Electric Parts

Soft starters DS and DM - Moeller Electric Parts

Soft starters DS and DM - Moeller Electric Parts

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>DS</strong>6 soft <strong>starters</strong><br />

14/36<br />

Technical Data Technical Data<br />

<strong>Soft</strong> <strong>starters</strong> <strong>Soft</strong> <strong>starters</strong><br />

<strong>DS</strong>6 <strong>Moeller</strong> HPL0211-2007/2008<br />

http://catalog.moeller.net http://catalog.moeller.net<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

<strong>DS</strong>6<br />

<strong>DS</strong>6-340-22K-MX <strong>DS</strong>6-340-30K-MX <strong>DS</strong>6-340-37K-MX <strong>DS</strong>6-340-45K-MX <strong>DS</strong>6-340-55K-MX <strong>DS</strong>6-340-75K-MX <strong>DS</strong>6-340-90K-MX <strong>DS</strong>6-340-110K-MX<br />

General<br />

St<strong>and</strong>ards IEC/EN 60947-4-2 IEC/EN 60947-4-2 IEC/EN 60947-4-2 IEC/EN 60947-4-2 IEC/EN 60947-4-2 IEC/EN 60947-4-2 IEC/EN 60947-4-2 IEC/EN 60947-4-2<br />

Approvals<br />

Climatic proofing Damp heat, constant according to IEC 60068-2-78; damp heat, cyclical, according to IEC 60068-2-10 Damp heat, constant according to IEC 60068-2-78; damp heat, cyclical, according to IEC 60068-2-10<br />

Ambient temperature °C 0…40, up to 60 at 1 % derating per Kelvin temperature rise 0…40, up to 60 at 1 % derating per Kelvin temperature rise<br />

Ambient temperature, storage °C –25…55 –25…55 –25…55 –25…55 –25…55 –25…55 –25…55 –25…55<br />

Altitude m 0…1000, above that 1 % derating per 100 m , up to 2000 m 0…1000, above that 1 % derating per 100 m , up to 2000 m<br />

Mounting position vertical vertical vertical vertical vertical vertical vertical vertical<br />

Degree of protection (Power connection) IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20<br />

Protection against direct contact Finger <strong>and</strong> back-of-h<strong>and</strong> proof Finger <strong>and</strong> back-of-h<strong>and</strong> proof<br />

Overvoltage category/pollution degree II/2 II/2 II/2 II/2 II/2 II/2 II/2 II/2<br />

Shock resistance 8 g/11 ms 8 g/11 ms 8 g/11 ms 8 g/11 ms 8 g/11 ms 8 g/11 ms 8 g/11 ms 8 g/11 ms<br />

Vibration resistance to EN 60721-3-2 g 2M2 2M2 2M2 2M2 2M2 2M2 2M2 2M2<br />

Average heat dissipation at rated load cycle W 7 10 13 18 25 24 30 42<br />

Dimensions (W x H x D) mm<br />

Radio interference level “A1” “A1” “A1” “A1” “A1” “A1” “A1” “A1”<br />

Weight kg 1.8 1.8 1.8 1.8 1.8 3.7 3.7 3.7<br />

Main conducting paths<br />

Rated operating voltage Ue V AC 230 – 460 230 – 460 230 – 460 230 – 460 230 – 460 230 – 460 230 – 460 230 – 460<br />

Supply frequency Hz 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60<br />

Rated operational current<br />

AC-51 (resistive loads) Ie A 41 55 68 81 99 135 160 200<br />

AC-53 (motor loads) Ie A 41 55 68 81 99 135 160 200<br />

Assigned motor rating (st<strong>and</strong>ard connection)<br />

230 V kW 11 15 15 22 30 30 45 55<br />

400 V kW 22 30 37 45 55 75 90 110<br />

460 V HP 30 40 50 60 75 100 125 150<br />

Overload cycle to IEC/EN 60947-4-2<br />

AC-51 (built-in bypass) 41 A: AC-53a: 3…5;<br />

75…10<br />

Terminal capacities<br />

Cable lengths<br />

Solid mm2 1 x (25 – 70)<br />

2 x (6 – 25)<br />

Flexible with ferrule mm2 Str<strong>and</strong>ed mm2 1 x (25 – 70)<br />

2 x (6 – 25)<br />

55 A: AC-53a: 3…5;<br />

75…10<br />

1 x (25 – 70)<br />

2 x (6 – 25)<br />

1 x (25 – 70)<br />

2 x (6 – 25)<br />

68 A: AC-53a: 3…5;<br />

75…10<br />

1 x (25 – 70)<br />

2 x (6 – 25)<br />

1 x (25 – 70)<br />

2 x (6 – 25)<br />

81 A: AC-53a: 3…5;<br />

75…10<br />

1 x (25 – 70)<br />

2 x (6 – 25)<br />

1 x (25 – 70)<br />

2 x (6 – 25)<br />

99 A: AC-53a: 3…5; 75…10<br />

99 A: AC-53a: 3…5; 75…10<br />

1 x (25 – 70)<br />

2 x (6 – 25)<br />

1 x (25 – 70)<br />

2 x (6 – 25)<br />

135 A: AC-53a: 3…5; 75…10<br />

135 A: AC-53a: 3…5; 75…10<br />

1 x (4 – 185)<br />

2 x (4 – 70)<br />

1 x (4 – 185)<br />

2 x (4 – 70)<br />

Solid or str<strong>and</strong>ed AWG 1 x (12 – 2/0) 1 x (12 – 2/0) 1 x (12 – 2/0) 1 x (12 – 2/0) 1 x (12 – 2/0) 1 x (12…350 kcmil)<br />

2 x (12 – 00)<br />

160 A: AC-53a: 3…5; 75…10<br />

160 A: AC-53a: 3…5; 75…10<br />

1 x (4 – 185)<br />

2 x (4 – 70)<br />

1 x (4 – 185)<br />

2 x (4 – 70)<br />

1 x (12…350 kcmil)<br />

2 x (12 – 00)<br />

200 A: AC-53a: 3…5; 75…10<br />

200 A: AC-53a: 3…5; 75…10<br />

1 x (4 – 185)<br />

2 x (4 – 70)<br />

1 x (4 – 185)<br />

2 x (4 – 70)<br />

1 x (12…350 kcmil)<br />

2 x (12 – 00)<br />

2 x 9 x 0.8 2 x 9 x 0.8 2 x 9 x 0.8 2 x 9 x 0.8<br />

B<strong>and</strong> min. mm 2 x 9 x 0.8 2 x 9 x 0.8 2 x 9 x 0.8 2 x 9 x 0.8 9 x 9 x 0.9 10 x 16 x 0.8 10 x 16 x 0.8 10 x 16 x 0.8<br />

max. mm 9 x 9 x 0.9 9 x 9 x 0.9 9 x 9 x 0.9 9 x 9 x 0.9<br />

Tightening torque Nm<br />

Control cables<br />

Solid mm2 1 x (0.5 – 2.5)<br />

2 x (0.5 – 1.0)<br />

Flexible with ferrule mm2 1 x (0.5 – 1.5)<br />

2 x (0.5 – 0.75)<br />

Str<strong>and</strong>ed mm2 1 x (0.5 – 1.5)<br />

2 x (0.5 – 1.0)<br />

Solid or str<strong>and</strong>ed AWG 1 x (21 – 14)<br />

2 x (21 – 18)<br />

1 x (0.5 – 2.5)<br />

2 x (0.5 – 1.0)<br />

1 x (0.5 – 1.5)<br />

2 x (0.5 – 0.75)<br />

1 x (0.5 – 1.5)<br />

2 x (0.5 – 1.0)<br />

1 x (21 – 14)<br />

2 x (21 – 18)<br />

1 x (0.5 – 2.5)<br />

2 x (0.5 – 1.0)<br />

1 x (0.5 – 1.5)<br />

2 x (0.5 – 0.75)<br />

1 x (0.5 – 1.5)<br />

2 x (0.5 – 1.0)<br />

1 x (21 – 14)<br />

2 x (21 – 18)<br />

1 x (0.5 – 2.5)<br />

2 x (0.5 – 1.0)<br />

1 x (0.5 – 1.5)<br />

2 x (0.5 – 0.75)<br />

1 x (0.5 – 1.5)<br />

2 x (0.5 – 1.0)<br />

1 x (21 – 14)<br />

2 x (21 – 18)<br />

1 x (0.5 – 2.5)<br />

2 x (0.5 – 1.0)<br />

1 x (0.5 – 1.5)<br />

2 x (0.5 – 0.75)<br />

1 x (0.5 – 1.5)<br />

2 x (0.5 – 1.0)<br />

1 x (21 – 14)<br />

2 x (21 – 18)<br />

1 x (0.5 – 2.5)<br />

2 x (0.5 – 1.0)<br />

1 x (0.5 – 1.5)<br />

2 x (0.5 – 0.75)<br />

1 x (0.5 – 1.5)<br />

2 x (0.5 – 1.0)<br />

1 x (21 – 14)<br />

2 x (21 – 18)<br />

1 x (0.5 – 2.5)<br />

2 x (0.5 – 1.0)<br />

1 x (0.5 – 1.5)<br />

2 x (0.5 – 0.75)<br />

1 x (0.5 – 1.5)<br />

2 x (0.5 – 1.0)<br />

1 x (21 – 14)<br />

2 x (21 – 18)<br />

flat conductor<br />

Tightening torque Nm 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4<br />

Screwdriver (PZ: Pozidriv) mm 0.6 x 3.5 0.6 x 3.5 0.6 x 3.5 0.6 x 3.5 0.6 x 3.5 0.6 x 3.5 0.6 x 3.5 0.6 x 3.5<br />

Notes Rated impulse withst<strong>and</strong> voltage:<br />

•1.2 ms/50 ms (rise time/fall time of the pulse to IEC/EN 60947-2 or -3)<br />

• Applies for control circuit/power section/enclosure<br />

For <strong>Moeller</strong> <strong>Electric</strong> Sales <strong>and</strong> Support call KMparts.com (866) 595-9616<br />

1 x (0.5 – 2.5)<br />

2 x (0.5 – 1.0)<br />

1 x (0.5 – 1.5)<br />

2 x (0.5 – 0.75)<br />

1 x (0.5 – 1.5)<br />

2 x (0.5 – 1.0)<br />

1 x (21 – 14)<br />

2 x (21 – 18)<br />

14/37<br />

<strong>DS</strong>6 soft <strong>starters</strong>

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!