Section 2.1<br />

LES PHYSIC PARAMÈTRES FACTORS<br />

PHYSIQUES<br />

Air stability according to the ASHRAE standards<br />

ASHRAE Conditions<br />

(Stability of the air for the balancing)<br />

The duct linking the elbow to the diffuser should have<br />

at least 7.5 to 8 times its diameter.<br />

20“<br />

R : 1.5 X D<br />

Air<br />

DAL 358 diffuser<br />

(Provide with plenum and stabilizing plate)<br />

The plenum have a maximum height of 13.5”<br />

and assures a stability of the air no matter how you<br />

attached it.<br />

H = (7.5 À 8) D<br />

Note : Can reduce at 10” but optimal performance at 13.5”.<br />

80”<br />

H<br />

Stabilizing plate<br />

TOTAL : 103”<br />

13.5 “<br />

D : Ø 10”<br />

3 “