Section 1.5<br />
COMFORT FACTORS<br />
Temperature difference<br />
12˚C<br />
12˚C<br />
Comfort level<br />
Human height<br />
6 ft (1.8 m)<br />
∆To = Tr -To<br />
10 = 22 - 12<br />
22˚C<br />
∆Txy = Tr -Txy<br />
2.5 = 22 - 19.5 (standard)<br />
0.6 = 22 - 21.4 (<strong>NAD</strong>)<br />
∆Txy<br />
∆To<br />
∆Txy<br />
∆To<br />
= 0.25 (standard)<br />
= 0.06 (<strong>NAD</strong>)<br />
Thermostat<br />
5 ft<br />
(1,4 m)<br />
9 ft<br />
- The <strong>NAD</strong> induction reduces the temperature difference in the occupied zone by 15 to 18 times.<br />
- The temperature difference at the output of the diffuser: 10°C<br />
- The temperature difference in the occupied zone : 0.6°C with high induction compared<br />
to 2.5°C with standard diffusion.