21.01.2015 Views

AIR COMP ACT AIR COMP ACT - Euroconfort

AIR COMP ACT AIR COMP ACT - Euroconfort

AIR COMP ACT AIR COMP ACT - Euroconfort

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

■ 2-way mixing box: CM2<br />

Air handling<br />

units<br />

<strong>AIR</strong> <strong>COMP</strong><strong>ACT</strong><br />

Box enabling fresh air and return air to be mixed by a moving vane ensuring flow metering and distribution.<br />

Manual and motorisable control.<br />

■ 3-way mixing box: CM3<br />

Box enabling removal of extracted air, introduction of fresh air and<br />

air recycling via the intermediary of two moving vanes ensuring<br />

flow metering and distribution.<br />

Manual and motorisation control possible.<br />

HI HS SI<br />

■ Straight or Curved Plenums: PLD PRS<br />

Can be mounted on either intake or discharge.<br />

2 plenum types:<br />

- intake or direct discharge: frame with double deflection<br />

grille, length 25 mm.<br />

- intake or discharge at RIGHT ANGLE: fitted with a double<br />

deflection grille, length 330 mm.<br />

PLD<br />

PRS<br />

■ Filtration<br />

In addition to a full section G4 filter base assembly,<br />

the following solutions are available: G4, F5 pleated, F6-F7-<br />

F8-F9 rigid pockets in universal sizes, with a compression<br />

system starting at filtration efficiency class F6.<br />

- Pressure taps mounted as standard on each stage.<br />

- Optional liquid filled pressure gauge.<br />

■ Hydraulic or evaporator coil in the AHU or<br />

vertical unit. CFV<br />

The coils are totally DRAINABLE. Piping is fitted with threaded<br />

ends with purge and drain plugs (Ø 1/8’’).<br />

- In heating mode:<br />

Size 25: 1, 2, and 3-row coils are available,<br />

Size 40 and 60: 1, 2, and 4-row coils are available,<br />

A frost protection thermostat with automatic reset can<br />

be installed on the coil.<br />

- In refrigeration mode:<br />

For each size there are 3, 4, and 6-row chilled water coils and<br />

3, 6 rows of direct expansion coils.<br />

The section is fitted with an eliminator, maximum face velocity:<br />

3.1 m/s and a stainless steel condensate container.<br />

Container isolation option using closed-cell foam.<br />

For vertical applications, max 4 rows in the CFV unit.<br />

2<br />

<strong>AIR</strong> CONDITIONING - HEATING - REFRIGERATION - <strong>AIR</strong> HANDLING - HEAT EXCHANGE - NA 08.637 A