23.01.2015 Views

STANDARD HANDBOOK OF PETROLEUM & NATURAL GAS ...

STANDARD HANDBOOK OF PETROLEUM & NATURAL GAS ...

STANDARD HANDBOOK OF PETROLEUM & NATURAL GAS ...

SHOW MORE
SHOW LESS
  • No tags were found...

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

416 Auxiliary Equipment<br />

time switch that can start and stop the motor according to a predetermined program,<br />

a timing relay that delays the start of the motor following a power failure, and lightning<br />

arresters. Pushbutton control is also provided.<br />

Power-Factor Correction. The induction motors used for oil-well pumping have<br />

high starting torques with relatively low power factors. Also, the average load on<br />

these motors is fairly low. Therefore, it is advisable to consider the installation of<br />

capacitors to avoid paying the penalty imposed by most power companies for lowpower<br />

factor. They will be installed at the individual motors and switched with them,<br />

if voltage drop in the distribution system is to be corrected as well as power factor.<br />

Otherwise they may be installed in large banks at the distribution center, if it is more<br />

economical to do so.<br />

Oil Pipelines. The main pumps for an oil pipeline usually driven by 3,600 rpm<br />

induction electric motors having NEMA Design B characteristics. Full-voltage starting<br />

is used. Figure 3-13 shows a typical pumping station diagram. Such pumping stations<br />

are located at the beginning of the pipeline and at intervals along the line. Intermediate<br />

or booster stations must be capable of operating under varying conditions due to<br />

differences in liquid gravity, withdrawals at intermediate points, and the shutting<br />

down of other booster stations. Pumping stations often contain two or three pumps<br />

connected in series, with bypass arrangements using check valves across each pump.<br />

The pumps may all be of the same capacity, or one of them may be half size. By<br />

operating the pumps singly or together, a range of pumping capacities can be achieved.<br />

Throttling of pump discharge may also be used to provide finer control and to permit<br />

operation when pump suction pressure may be inadequate for full flow operation.<br />

Pumping stations are often unattended and may be remotely controlled by radio<br />

or telephone circuits.<br />

Motor enclosures for outdoor use are NEMA weather-protected Type 11, totally<br />

enclosed, fan-cooled, or drip-proof with weather protection. Motors of the latter<br />

type are widely used. Not only are they less expensive than the other types, but<br />

they also have a service factor of 1.15. The above enclosure types are all suitable<br />

for the Class I, Group D, Division 2 classifications usually encountered.<br />

If the pumps are located indoors, a Division 1 classification is likely to apply. Motors<br />

must be Class I, group D, explosion-proof, or they may be separately ventilated with<br />

clean outside air brought to the motor by fans. Auxiliary devices such as alarm contacts<br />

on the motor must be suitable for the area classification. The installed costs, overall<br />

efficiencies, and service factors associated with the enclosures that are available will<br />

influence the selection.<br />

Throttling<br />

Motoroperated<br />

valve<br />

8<br />

I 1<br />

I I<br />

Pump No. 1 PumpNo. 2 PumpNo. 3<br />

Figure 3-13. Typical oil pipeline pump station [lo].

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!