<strong>1.</strong> General Details:<br />
Air System Name ............................................................... Auditório<br />
Equipment Class ................................................. Chilled Water AHU<br />
Air System Type ..................................................... S<strong>in</strong>gle Zone CAV<br />
Number of zones .............................................................................. 1<br />
<strong>2.</strong> System Components:<br />
Ventilation Air Data:<br />
Airflow Control .................................... Constant Ventilation Airflow<br />
Ventilation Siz<strong>in</strong>g Method ...................... Sum of Space OA Airflows<br />
Unocc. Damper Position ......................................................... Closed<br />
Damper Leak Rate ........................................................................... 5 %<br />
Outdoor Air CO2 Level ................................................................. 400 ppm<br />
Ventilation Reclaim Data:<br />
Reclaim Type .............................................................. Sensible Heat<br />
Thermal Efficiency .......................................................................... 50 %<br />
Input kW ........................................................................................ 0.0 kW<br />
Schedule ............................................................... JFMAMJJASOND<br />
Central Cool<strong>in</strong>g Data:<br />
Supply Air Temperature .............................................................. 15.0 °C<br />
Coil Bypass Factor .................................................................... 0.100<br />
Cool<strong>in</strong>g Source ............................................................ Chilled Water<br />
Schedule ............................................................... JFMAMJJASOND<br />
Capacity Control .... Temperature Reset by Greatest Zone Demand<br />
Max. Supply Temperature ........................................................... 15.0 °C<br />
Central Heat<strong>in</strong>g Data:<br />
Supply Temperature .................................................................... 40.0 °C<br />
Heat<strong>in</strong>g Source ................................................................. Hot Water<br />
Schedule ............................................................... JFMAMJJASOND<br />
Capacity Control .... Temperature Reset by Greatest Zone Demand<br />
M<strong>in</strong>. Supply Temperature ............................................................ 35.0 °C<br />
Supply Fan Data:<br />
Fan Type ................................................................. Forward Curved<br />
Configuration ..................................................................... Draw-thru<br />
Fan Performance ......................................................................... 800 Pa<br />
Overall Efficiency ........................................................................... 54 %<br />
Duct System Data:<br />
Supply Duct Data:<br />
Duct Heat Ga<strong>in</strong> ................................................................................. 0 %<br />
Duct Leakage ................................................................................... 0 %<br />
Return Duct or Plenum Data:<br />
Return Air Via ............................................................. Ducted Return<br />
Return Fan Data:<br />
Fan Type ................................................................. Forward Curved<br />
Fan Performance ......................................................................... 400 Pa<br />
Overall Efficiency ........................................................................... 54 %