C<strong>in</strong>ema VAC Floor – Space Load Summary for Auditory<br />
TABLE <strong>1.</strong><strong>1.</strong>A.<br />
COMPONENT LOADS FOR SPACE '' Auditorio '' IN ZONE '' Zone 1 ''<br />
DESIGN COOLING<br />
DESIGN HEATING<br />
COOLING DATA AT Sep 2300<br />
HEATING DATA AT DES HTG<br />
COOLING OA DB / WB 27.3 °C / 18.8 °C HEATING OA DB / WB 3.5 °C / <strong>2.</strong>3 °C<br />
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 20.0 °C<br />
Sensible Latent Sensible Latent<br />
SPACE LOADS Details (W) (W) Details (W) (W)<br />
W<strong>in</strong>dow & Skylight Solar Loads 0 m² 0 - 0 m² - -<br />
Wall Transmission 98 m² 59 - 98 m² 147 -<br />
Roof Transmission 0 m² 0 - 0 m² 0 -<br />
W<strong>in</strong>dow Transmission 0 m² 0 - 0 m² 0 -<br />
Skylight Transmission 0 m² 0 - 0 m² 0 -<br />
Door Loads 0 m² 0 - 0 m² 0 -<br />
Floor Transmission 266 m² 0 - 266 m² 575 -<br />
Partitions 0 m² 0 - 0 m² 0 -<br />
Ceil<strong>in</strong>g 0 m² 0 - 0 m² 0 -<br />
Overhead Light<strong>in</strong>g 1596 W 1303 - 0 0 -<br />
Task Light<strong>in</strong>g 0 W 0 - 0 0 -<br />
Electric Equipment 0 W 0 - 0 0 -<br />
People 308 20755 10842 0 0 0<br />
Infiltration - 0 0 - 0 0<br />
Miscellaneous - 0 0 - 0 0<br />
Safety Factor 5% / 5% 1106 542 5% 36 0<br />
>> Total Zone Loads - 23223 11384 - 757 0<br />
TABLE <strong>1.</strong><strong>1.</strong>B. ENVELOPE LOADS FOR SPACE '' Auditorio '' IN ZONE '' Zone 1 ''<br />
COOLING COOLING HEATIN G<br />
Area U-Value Shade TRANS SOLAR TRANS<br />
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)<br />
S EXPOSURE<br />
WALL 98 0.091 - 59 - 147