Functional Setup<br />

3.0 Functional Setup<br />

LCD CONTRAST<br />

ADJUSTMENT<br />

JW1, JW2, JW3 ARE<br />

FOR FACTORY USE<br />

LEAVE JUMPERS<br />

JW2 AND JW3 IN<br />

PLACE.<br />

VR1<br />

JW1<br />

JW2<br />

JW3<br />

P2<br />

SYSTEM<br />

RESET<br />

SIGNAL<br />

SILENCE<br />

SYSTEM NORMAL<br />

18:01 MON 2011-02-07<br />

A.C. ON ALARM SUPV TRBL CPU FAIL<br />

1<br />

2<br />

ABC<br />

3<br />

DEF<br />

ENTER<br />

FIRE<br />

DRILL<br />

4<br />

5<br />

6<br />

GHI JKL MNO<br />

MENU<br />

THESE PINS ARE<br />

FOR FACTORY USE<br />

ONLY<br />

24V IN/OUT<br />

- +<br />

CUT JUMPER JW8 TO<br />

MAKE <strong>RAM</strong>-<strong>300LCD</strong> AN<br />

ANCILLARY DEVICE.<br />

JW8<br />

BUZZER<br />

SILENCE<br />

ON<br />

LAMP<br />

TEST<br />

1 2 3 4 5 6 7 8<br />

SW31<br />

Figure 3<br />

7<br />

8<br />

9<br />

PRS TUV WXY<br />

*<br />

0<br />

QZ<br />

SW31 DIP Switch<br />

for various<br />

system functions<br />

#<br />

CANCEL<br />

INFO<br />

SW30<br />

ON<br />

1 2 3 4<br />

RS-485 IN/OUT<br />

+ - S<br />

SW30 DIP Switch for annunciator<br />

address setting. Valid addresses<br />

1 to 7.<br />

Annunciator Component Descriptions<br />

P1<br />

THIS<br />

CONNECTOR IS<br />

FOR FACTORY<br />

USE ONLY<br />

Place the 120 ohm<br />

EOL resistor between<br />

+ <strong>and</strong> - terminals of<br />

the RS-485 on the<br />

last annunciator<br />

only.<br />

3.1 Jumpers<br />

Table 1 Jumpers<br />

Jumper<br />

JW1<br />

JW2<br />

JW3<br />

JW8<br />

Jumper Function<br />

FACTORY USE ONLY (JUMPER OFF)<br />

FACTORY USE ONLY (JUMPER INSTALLED)<br />

FACTORY USE ONLY (JUMPER INSTALLED)<br />

CUT jumper to set the <strong>RAM</strong>-<strong>300LCD</strong> as an ancillary device. Use NP-2051 blank labels<br />

to cover the System Reset, Signal Silence, Fire Drill, Enter, Menu <strong>and</strong> Cancel buttons<br />

for the Ancillary Device Feature. Only Buzzer Silence, Lamp Test <strong>and</strong> Info are used.<br />

3.2 Potentiometer<br />

VR1 is a potentiometer used for LCD contrast adjustment <strong>and</strong> is located in the top left corner<br />

of the <strong>RAM</strong>-<strong>300LCD</strong> board.<br />