Data sheet<br />

2004 0<br />

MV vacuum circuit breaker<br />

<strong>Evolis</strong><br />

<strong>17.5</strong> <strong>kV</strong><br />

<strong>Evolis</strong> circuit breaker is used to<br />

protect and control MV public or<br />

industrial distribution network.<br />

DE30105<br />

<strong>Evolis</strong> is an indoor switchgear<br />

b Rated voltage from 7.2 <strong>kV</strong> to <strong>17.5</strong> <strong>kV</strong><br />

b Rated short-circuit breaking current<br />

from 25 kA to 40 kA<br />

b Rated normal current<br />

from 630 A to 2500 A.<br />

<strong>Evolis</strong> is available in 2 versions:<br />

b withdrawable with cradle<br />

b fixed: can be completed by kits<br />

and delivered in separate components.<br />

Conformity with standards<br />

b IEC 60694: common specifications for high voltage switchgear<br />

and controlgear standards<br />

b IEC 62271-100: high voltage alternating current circuit breaker<br />

b IEC 62271-200 (previously IEC 60298): AC metal-enclosed switchgear<br />

and controlgear for rated voltages above 1 <strong>kV</strong> and up to and including 52 <strong>kV</strong>.<br />

Certification<br />

b By independent laboratories in accordance with ISO/IEC 17025<br />

and EN 45011 standards<br />

b Our factories implement a quality system certified to ISO 9001<br />

and ISO 9002 standards by IQNET.<br />

Installation<br />

b Fixed or withdrawable<br />

b Designed for retrofit<br />

b Cradle can be delivered separately<br />

b Fixed or variable pole center distance connections.<br />

Operation<br />

b Operating mechanism is identical to that on the Merlin Gerin Masterpact<br />

LV power circuit breaker<br />

b Metal protection shutter on cradle<br />

b Racking in/out operation possible in the cubicle with the door closed.


Electrical characteristics according to IEC 62271-100<br />

Circuit breaker<br />

A full range of accessories and auxiliaries<br />

factory-mounted or delivered separately<br />

b Electric motor (MCH)<br />

b Undervoltage release (MN)<br />

b Shunt opening release (MX)<br />

b Low energy release (MITOP)<br />

b Shunt closing release (YF)<br />

b Auxiliary contacts (OF, SDE, PF, CE/CD)<br />

b Operations counter (CDM)<br />

b Locking by padlocks and/or keylocks/sealing.<br />

Common characteristics according to IEC 62271-100<br />

(edition 05/2001)<br />

Rated frequency fr (Hz) 50 & 60<br />

Rated duration of short-circuit tk (s) 3<br />

Rated making current (kA) peak 2.5 & 2.6 Isc<br />

Maximum rated operations sequences<br />

Approximate operating times opening (ms) < 50<br />

closing (ms) < 65<br />

Endurance mechanical class M2<br />

Capacitive current breaking<br />

7P1<br />

630<br />

7P1<br />

1250<br />

7P1<br />

2500<br />

electrical<br />

O-0.3 s-CO-15 s-CO<br />

class E2<br />

class C1<br />

Rated voltage Ur (<strong>kV</strong>) rms 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 12 12 12 12 12<br />

Rated insulation voltage (50/60 Hz) Ud (<strong>kV</strong>) rms 20 20 20 20 20 20 20 20 20 28 28 28 28 28<br />

Rated insulation voltage (lightning impulse) Up (<strong>kV</strong>) peak 60 60 60 60 60 60 60 60 60 75 75 75 75 75<br />

Rated short-circuit breaking current Isc (kA) rms 25 25 25 31.5 31.5 31.5 40 40 40 25 25 25 31.5 31.5<br />

Rated normal current (–25 +40°C) Ir (A) rms 630 1250 2500 630 1250 2500 630 1250 2500 630 1250 2500 630 1250<br />

Circuit breaker<br />

12P2<br />

2500<br />

12P3<br />

630<br />

Rated voltage Ur (<strong>kV</strong>) rms 12 12 12 12 <strong>17.5</strong> <strong>17.5</strong> <strong>17.5</strong> <strong>17.5</strong> <strong>17.5</strong> <strong>17.5</strong> <strong>17.5</strong> <strong>17.5</strong> <strong>17.5</strong><br />

Rated insulation voltage (50/60 Hz) Ud (<strong>kV</strong>) rms 28 28 28 28 38 38 38 38 38 38 38 38 38<br />

Rated insulation voltage (lightning impulse) Up (<strong>kV</strong>) peak 75 75 75 75 95 95 95 95 95 95 95 95 95<br />

Rated short-circuit breaking current Isc (kA) rms 31.5 40 40 40 25 25 25 31.5 31.5 31.5 40 40 40<br />

Rated normal current (–25 +40°C) Ir (A) rms 2500 630 1250 2500 630 1250 2500 630 1250 2500 630 1250 2500<br />

7P2<br />

630<br />

12P3<br />

1250<br />

7P2<br />

1250<br />

12P3<br />

2500<br />

7P2<br />

2500<br />

17P1<br />

630<br />

7P3<br />

630<br />

17P1<br />

1250<br />

7P3<br />

1250<br />

17P1<br />

2500<br />

7P3<br />

2500<br />

17P2<br />

630<br />

12P1<br />

630<br />

17P2<br />

1250<br />

12P1<br />

1250<br />

17P2<br />

2500<br />

12P1<br />

2500<br />

17P3<br />

630<br />

12P2<br />

630<br />

17P3<br />

1250<br />

12P2<br />

1250<br />

17P3<br />

2500<br />

Withdrawable version<br />

Dimensions and weights<br />

DE30106<br />

Withdrawable version<br />

7.2 to 12 <strong>kV</strong> - 630 & 1250 A<br />

25 kA<br />

7.2 to <strong>17.5</strong> <strong>kV</strong> - 630 & 1250 A<br />

25 & 31.5 kA<br />

7.2 to <strong>17.5</strong> <strong>kV</strong> - 2500 A<br />

25 & 31.5 kA<br />

7.2 to <strong>17.5</strong> <strong>kV</strong> - 630 to 2500 A<br />

40 kA<br />

Phase distance<br />

(mm)<br />

W<br />

(mm)<br />

H<br />

(mm)<br />

D<br />

(mm)<br />

Weight<br />

(kg)<br />

145 576 965 1140 165<br />

185 686 965 1140 174<br />

240 866 965 1140 272<br />

240 866 965 1140 272<br />

DE30107<br />

Fixed version<br />

Schneider Electric Industries SAS<br />

Electrical Distribution Communication<br />

F-38050 Grenoble Cedex 9<br />

France<br />

Tel.: +33 (0)4 76 57 60 60<br />

http;//www.schneider-electric.com<br />

http;//www.mvproduct.merlin-gerin.com<br />

Fixed version<br />

7.2 to 12 <strong>kV</strong> - 630 & 1250 A<br />

25 kA<br />

7.2 to <strong>17.5</strong> <strong>kV</strong> - 630 & 1250 A<br />

25 & 31.5 kA<br />

7.2 to <strong>17.5</strong> <strong>kV</strong> - 2500 A<br />

25 & 31.5 kA<br />

7.2 to <strong>17.5</strong> <strong>kV</strong> - 630 & 2500 A<br />

40 kA<br />

d: phase distance<br />

(mm)<br />

As standards, specifications and designs change from time to time, please ask for confirmation<br />

of the information given in this publication.<br />

Publishing: Schneider Electric<br />

Design: communication Schneider Electric MT<br />

Production: Graphème<br />

Printing: Imprimerie du Pont de Claix<br />

This document has been<br />

printed on ecological paper<br />

AMTED300001EN 06/2004<br />

W<br />

(mm)<br />

H<br />

(mm)<br />

D<br />

(mm)<br />

145 470 535 429 51<br />

185 550 535 429 55<br />

240 660 535 429 79<br />

240 660 535 429 79<br />

Weight<br />

(kg)<br />

© 2004 Schneider Electric - All rights reserved