01.07.2015 Views

Soft starters - Trinet

Soft starters - Trinet

Soft starters - Trinet

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Schemes (continued) <strong>Soft</strong> <strong>starters</strong> 0<br />

Altistart 48 soft start - soft stop units<br />

Recommended application diagram for LSP/HSP motor, non-reversing with starter line and bypass<br />

contactors<br />

1/L1<br />

3/L2<br />

5/L3<br />

CL1<br />

2/T1<br />

A2<br />

4/T2<br />

B2<br />

6/T3<br />

C2<br />

RUN<br />

STOP<br />

LI3<br />

LI4<br />

+24V<br />

LO+<br />

LO1<br />

LO2<br />

2<br />

4<br />

6<br />

- KM1<br />

2<br />

4<br />

6<br />

1<br />

3<br />

5<br />

1<br />

3<br />

5<br />

CL2<br />

- KM3<br />

2<br />

4<br />

6<br />

1<br />

3<br />

5<br />

- Q1<br />

1 2<br />

- T1<br />

1 2<br />

220<br />

1 2<br />

0<br />

Q3<br />

(1)<br />

(2)<br />

A1<br />

AO1<br />

COM<br />

PTC1<br />

PTC2<br />

R1A<br />

R1C<br />

R2A<br />

R2C<br />

R3A<br />

R3C<br />

(3)<br />

KA1<br />

KM2<br />

- KM5<br />

- KM2<br />

U2<br />

V2<br />

W2<br />

M1<br />

3<br />

U1<br />

V1<br />

W1<br />

Select the components to connect, according to the descriptions below, from the association tables on pages 60525/2 to 60525/11.<br />

(1) For type 2 coordination (according to IEC 60947-4-2), install fast-acting fuses to ensure that the starter will be protected in the event of a short-circuit.<br />

(2) Insert a transformer if the line voltage is different to that defined for the control circuit (see page 60521/2).<br />

(3) Assign logic input LI3 to "activate the adjustment functions of the 2 nd motor".<br />

(4) Assign relay R1 as the "isolating relay". Beware of the operating limits of the contacts (see Characteristics page 60521/2), for example when connecting to high<br />

rating contactors.<br />

220 V<br />

KM1<br />

S1<br />

Emergency stop<br />

S2<br />

Q1<br />

S4<br />

1<br />

2<br />

KM2<br />

KM5<br />

A1<br />

R2C R2A<br />

(4)<br />

S3<br />

KA1<br />

A1<br />

R1C R1A<br />

(4)<br />

KM5<br />

KM2<br />

KA1 KM1 KM2 KM5<br />

KM3<br />

S4 = 1 : low speed<br />

= 2 : high speed<br />

0<br />

Components to connect depending on the types of coordination and voltages<br />

Designation<br />

Description<br />

M1<br />

Motor<br />

A1<br />

Starter (standard applications and severe applications)<br />

Q1<br />

Circuit-breaker or switch/fuses<br />

Q3<br />

3 FA fuses<br />

KM1, KM2, KM3, KM5, KA1<br />

Contactors and relays<br />

S1, S2, S3 Control (separate parts XB2 or XB2 M)<br />

Schneider Electric<br />

60524_Ver1.10-EN.fm/5

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!