Schemes (continued) <strong>Soft</strong> <strong>starters</strong> 0<br />
Altistart 48 soft start - soft stop units<br />
Recommended application diagram for LSP/HSP motor, non-reversing with starter line and bypass<br />
contactors<br />
1/L1<br />
3/L2<br />
5/L3<br />
CL1<br />
2/T1<br />
A2<br />
4/T2<br />
B2<br />
6/T3<br />
C2<br />
RUN<br />
STOP<br />
LI3<br />
LI4<br />
+24V<br />
LO+<br />
LO1<br />
LO2<br />
2<br />
4<br />
6<br />
- KM1<br />
2<br />
4<br />
6<br />
1<br />
3<br />
5<br />
1<br />
3<br />
5<br />
CL2<br />
- KM3<br />
2<br />
4<br />
6<br />
1<br />
3<br />
5<br />
- Q1<br />
1 2<br />
- T1<br />
1 2<br />
220<br />
1 2<br />
0<br />
Q3<br />
(1)<br />
(2)<br />
A1<br />
AO1<br />
COM<br />
PTC1<br />
PTC2<br />
R1A<br />
R1C<br />
R2A<br />
R2C<br />
R3A<br />
R3C<br />
(3)<br />
KA1<br />
KM2<br />
- KM5<br />
- KM2<br />
U2<br />
V2<br />
W2<br />
M1<br />
3<br />
U1<br />
V1<br />
W1<br />
Select the components to connect, according to the descriptions below, from the association tables on pages 60525/2 to 60525/11.<br />
(1) For type 2 coordination (according to IEC 60947-4-2), install fast-acting fuses to ensure that the starter will be protected in the event of a short-circuit.<br />
(2) Insert a transformer if the line voltage is different to that defined for the control circuit (see page 60521/2).<br />
(3) Assign logic input LI3 to "activate the adjustment functions of the 2 nd motor".<br />
(4) Assign relay R1 as the "isolating relay". Beware of the operating limits of the contacts (see Characteristics page 60521/2), for example when connecting to high<br />
rating contactors.<br />
220 V<br />
KM1<br />
S1<br />
Emergency stop<br />
S2<br />
Q1<br />
S4<br />
1<br />
2<br />
KM2<br />
KM5<br />
A1<br />
R2C R2A<br />
(4)<br />
S3<br />
KA1<br />
A1<br />
R1C R1A<br />
(4)<br />
KM5<br />
KM2<br />
KA1 KM1 KM2 KM5<br />
KM3<br />
S4 = 1 : low speed<br />
= 2 : high speed<br />
0<br />
Components to connect depending on the types of coordination and voltages<br />
Designation<br />
Description<br />
M1<br />
Motor<br />
A1<br />
Starter (standard applications and severe applications)<br />
Q1<br />
Circuit-breaker or switch/fuses<br />
Q3<br />
3 FA fuses<br />
KM1, KM2, KM3, KM5, KA1<br />
Contactors and relays<br />
S1, S2, S3 Control (separate parts XB2 or XB2 M)<br />
Schneider Electric<br />
60524_Ver1.10-EN.fm/5