E. ELECTRICAL<br />

1. General. Install wiring <strong>and</strong> ground <strong>boiler</strong> in<br />

accordance with authority having jurisdiction or in<br />

absence of such requirements National Electrical<br />

Code, ANSI/NFPA 70 <strong>and</strong>/or CSA C22.1 Electrical<br />

Code.<br />

WARNING<br />

Failure to properly wire electrical<br />

connections to the <strong>boiler</strong> may result in<br />

serious physical harm. DO NOT ATTACH<br />

ADDITIONAL J-Box to back or top of <strong>boiler</strong><br />

jacket.<br />

WARNING<br />

The wiring diagrams contained in this<br />

manual are for reference purposes only.<br />

Each <strong>boiler</strong> may be wired differently<br />

according to the specifications given to<br />

Thermal Solutions at the time the <strong>boiler</strong> was<br />

purchased. Always use the wiring diagram<br />

provided with the <strong>boiler</strong>. If the wiring<br />

diagram provided with the <strong>boiler</strong> is<br />

unavailable, STOP all wiring work <strong>and</strong><br />

contact Thermal Solutions for a<br />

replacement diagram.<br />

DANGER<br />

Positively assure all electrical connections<br />

are unpowered before attempting<br />

<strong>installation</strong> or <strong>service</strong> of electrical<br />

components or connections of the <strong>boiler</strong> or<br />

building. Lock out all electrical boxes with<br />

padlock once power is turned off.<br />

2. Connect the main power supply <strong>and</strong> ground from<br />

fused disconnect to proper <strong>boiler</strong> electrical leads<br />

located in the junction box at the rear of the <strong>boiler</strong>.<br />

Refer to electrical consumption plate on <strong>boiler</strong><br />

jacket.<br />

3. Remove factory supplied jumper wire from<br />

terminals 4 <strong>and</strong> 5. Connect field supplied safety<br />

limits or devices (low water cut-off, temperature<br />

limit etc.) in <strong>series</strong> using proper terminals provided<br />

in <strong>boiler</strong> electrical cabinet. Refer to wiring diagram<br />

supplied with <strong>boiler</strong> for wiring information. Refer to<br />

Figures 9a, 9b, <strong>and</strong> 9c, for typical wiring diagrams.<br />

Refer to Figure 1, for electrical requirements for<br />

WARNING<br />

Do not directly connect low voltage (24 volt,<br />

milliamp etc.) controls to this <strong>boiler</strong>. If low<br />

voltage controls are desired, isolating<br />

relays must be used.<br />

WARNING<br />

Never jump out any safety controls.<br />

5. Following pages have sample wiring diagrams.<br />

Contact Thermal Solutions Representative or visit<br />

website (www.thermalsolutions.com) for current<br />

wiring options.<br />

6. An as-built wiring diagram is included with every<br />

<strong>boiler</strong> when it ships.<br />

CAUTION<br />

Each <strong>boiler</strong> must be protected with a<br />

dedicated properly sized fused disconnect.<br />

WARNING<br />

Electrical power may be supplied from more<br />

than one <strong>service</strong>. Make sure all power is off<br />

before attempting any electrical work.<br />