PERIODIC MAINTENANCE RECOMMENDED CHECK LIST<br />

Frequency Component/Item Recommended Test<br />

Daily<br />

Maintenance<br />

Weekly<br />

Maintenance<br />

Monthly<br />

Maintenance<br />

Semi-Annual<br />

Maintenance<br />

Annual<br />

Maintenance<br />

As-Required<br />

Gauges, monitors, <strong>and</strong> indicators<br />

Gauges, monitors, <strong>and</strong> indicators<br />

Burner flame<br />

Low Draft, fan air pressure, <strong>and</strong> damper<br />

position interlocks<br />

Igniter<br />

Flame signal strength<br />

Flame failure detection system<br />

Firing rate control<br />

Pilot <strong>and</strong>/or main fuel valves<br />

Low-water fuel cutoff<br />

Flue, vent, stack, or outlet dampers<br />

Gas pressure interlocks<br />

Gauges, monitors, <strong>and</strong> indicators<br />

Flame failure detection system<br />

Condensate drain tubes<br />

Air filter<br />

Interlocks <strong>and</strong> valves<br />

Flue, vent, stack, or outlet dampers<br />

Flame failure detection system<br />

Pilot <strong>and</strong>/or main fuel valves<br />

Pilot <strong>and</strong>/or main fuel valves<br />

Flame safeguard<br />

Air Filter<br />

Boiler trim<br />

High limit <strong>and</strong> <strong>operating</strong> temp. controls<br />

Low-water fuel cutoff<br />

Safety relief valves<br />

Make visual inspection <strong>and</strong> record readings.<br />

Check operation of <strong>boiler</strong> is as shown on page (46) of<br />

this manual.<br />

Make visual inspection of burner flame.<br />

Test low draft, fan, air pressure, <strong>and</strong> damper position<br />

interlocks according to <strong>instructions</strong> if so equipped<br />

Make visual inspection, check flame signal strength; log<br />

Read <strong>and</strong> log flame signal meter, read for both pilot <strong>and</strong><br />

main flames<br />

Close manual fuel supply for (1) pilot, (2) main fuel cock,<br />

<strong>and</strong>/or valve(s); check safety shutdown timing<br />

Check firing rate control, place RWF40 in manual<br />

mode <strong>and</strong> check high <strong>and</strong> low firing settings for proper<br />

operation<br />

Open limit switch <strong>and</strong> make aural <strong>and</strong> visual check;<br />

check valve position indicators <strong>and</strong> check fuel meters if<br />

so fitted<br />

Test low-water fuel cutoff device <strong>and</strong> alarm according to<br />

manufacturer’s <strong>instructions</strong><br />

Check components<br />

Test high <strong>and</strong> low gas pressure interlocks<br />

Recalibrate all indicating <strong>and</strong> recording gauges<br />

Check components<br />

Check drain tubes have liquid in trap <strong>and</strong> condensate is<br />

properly directed<br />

Check air filter<br />

Check piping <strong>and</strong> wiring of all interlocks <strong>and</strong> shut off<br />

valves if so equipped<br />

Measure carbon monoxide <strong>and</strong> oxygen levels <strong>and</strong><br />

temperature in flue products<br />

Conduct pilot turndown test according to manufacturer’s<br />

<strong>instructions</strong>. This test is required annually <strong>and</strong> after any<br />

adjustments to flame scanner mount or pilot burner<br />

Check all coils <strong>and</strong> diaphragms; test other <strong>operating</strong><br />

parts of all safety shutoff <strong>and</strong> control valves<br />

Perform leakage test on pilot <strong>and</strong> main gas <strong>and</strong>/or oil<br />

fuel valves, in accordance with <strong>instructions</strong><br />

Test purge timing according to manufacturer’s<br />

<strong>instructions</strong><br />

Replace (recommended)<br />

Remove lower front jacket panel <strong>and</strong> check for any signs<br />

of corrosion <strong>and</strong> leaks<br />

Test proper operation<br />

Recondition or replace<br />

Test safety relief valves in accordance with ASME Boiler <strong>and</strong><br />

Pressure Vessel Code, Sections VI <strong>and</strong> VII<br />

47