<strong>Thermal</strong> <strong>Solutions</strong> ProtoNode Start Up guide Page 10 of 32<br />

3 INTERFACING THE PROTONODE TO THERMAL SOLUTIONS TSBC BOILER<br />

CONTROLLER<br />

3.1 ProtoNode RER and LER showing connection ports<br />

RS-485 Port for<br />

Serial Field Protocol<br />

LonWorks<br />

Service Pin<br />

LonWorks Port<br />

(1) Modbus RTU to TSBC<br />

<strong>Controller</strong>s RS-485 Port<br />

10/100<br />

BaseT<br />

(1) (2) (1)<br />

(2)<br />

(2) Power +/- and FG<br />

9-30 VDC, 12-24 VAC<br />

Figure 4: ProtoNode RER (left) and LER (right)<br />

3.2 Wiring Connections to ProtoNode RER and LER<br />

ProtoNode 6 Pin Phoenix connector –<br />

Pinouts<br />

ProtoNode Pin # Pin assignment<br />

Pin 1 RS-485 +<br />

Pin 2 RS-485 -<br />

Pin 3<br />

RS-485 GND<br />

Pin 4 V +<br />

Pin 5 V -<br />

Pin 6<br />

FRAME GND<br />

ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com<br />

Tel: (408) 964 4444 Fax: (408) 964 4425 <strong>To</strong>ll Free: (800) 317 8319 x141 email: support@protocessor.com