<strong>Thermal</strong> <strong>Solutions</strong> ProtoNode Start Up guide Page 6 of 32<br />
2 BACNET/LONWORKS SETUP THROUGH PROTOCESSOR PROTONODE<br />
RER/LER<br />
2.1 Installation steps for the customer<br />
1. Record the information about the unit. (See Section 2.2)<br />
2. Set the BAUD rate to 19200 on the TSBC boiler controllers.<br />
3. Set the Modbus RTU device address on all the TSBC boiler controllers.<br />
4. Set the Modbus RTU Serial settings on the EVNI boiler controllers.<br />
5. If using BACnet MS/TP, set the BACnet MS/TP MAC Address on DIP Switch Bank A. (See section 2.3.2)<br />
6. Set the ProtoNode Node ID/Device Instance of the Field Protocol on DIP Switch Bank A. (See section<br />
2.3.3)<br />
7. Set the ProtoNode BAUD rate of the Field Protocol on DIP Switch Bank B. (See section 2.3.4)<br />
8. Set the ProtoNode Field Protocol on Dip Switch Bank S. (See Section 2.3.5)<br />
9. Enable the ProtoNode “Auto Discovery” mode on Dip Switch Bank S. (See section 2.3.6).<br />
10. Connect the ProtoNode to the Field protocol port and the TSBC’s RS-485 Modbus RTU port to the<br />
ProtoNode’s RS-485 interface. (See Section 3)<br />
11. Power up the ProtoNode RER and LER. It will take about 3 minutes for all the OEM devices to be<br />
discovered, and the configuration file to be built.<br />
12. Once the ProtoNode has finished creating the configuration file, set the “Auto Discovery” Dip Switch to<br />
“Off” to save the configuration settings.<br />
13. If the Field protocol is BACnet/IP or Modbus TCP, refer to Section 4 to run to run the ProtoNode web GUI<br />
utility program to change the IP address. No changes to the configuration file are necessary.<br />
2.2 Record Identification Data<br />
Each ProtoNode has a unique part number located on the underside of the unit. The numbers are as follows:<br />
<br />
<br />
FPC‐N34‐103‐116‐0799 supports TSBC controllers to BACnet MS/TP, or BACnet/IP.<br />
FPC‐N35‐103‐401‐0810 supports TSBC controllers to LonWorks.<br />
This number should be recorded, as it may be required for technical support.<br />