5.3 CONNECTING MORE THAN ONE DETECTOR (c<strong>on</strong>tinued)<br />
1. Open the cover of the first SMOKE DETECTOR (supplied as<br />
standard) and locate the screw terminal that the standard 10m<br />
cable is attached to.<br />
2. Remove the cable from the screw terminal by unscrewing the<br />
terminal screws.<br />
3. Cut the required length of “interc<strong>on</strong>nect” cable to c<strong>on</strong>nect the<br />
first SMOKE DETECTOR to the sec<strong>on</strong>d SMOKE DETECTOR<br />
and strip the ends.<br />
4. C<strong>on</strong>nect both the standard 10m cable (that plugs into the<br />
JUNCTION BOX 3 ) and the “interc<strong>on</strong>nect cable” to the<br />
screw terminal in the first SMOKE DETECTOR, making sure<br />
that the c<strong>on</strong>necti<strong>on</strong>s are tightened correctly.<br />
5. Open the cover of the sec<strong>on</strong>d SMOKE DETECTOR (opti<strong>on</strong>al)<br />
and locate the screw terminal.<br />
6. C<strong>on</strong>nect the other end of the “interc<strong>on</strong>nect cable” to the<br />
screw terminal in the sec<strong>on</strong>d SMOKE DETECTOR, making<br />
sure that the c<strong>on</strong>necti<strong>on</strong>s are tightened correctly.<br />
7. Using wire cutters remove the resistor, R56, from the screw<br />
terminal circuit board in the first SMOKE DETECTOR <strong>on</strong>ly.<br />
8. When installing more than <strong>on</strong>e additi<strong>on</strong>al SMOKE<br />
DETECTOR repeat steps 1-6 above, c<strong>on</strong>necting the third to<br />
the sec<strong>on</strong>d, the fourth to the third etc.<br />
IMPORTANT: When installing more than <strong>on</strong>e additi<strong>on</strong>al<br />
SMOKE DETECTOR each SMOKE DETECTOR screw<br />
terminal circuit board should have resistor R56 removed as in<br />
step 7 above, apart from the last SMOKE DETECTOR<br />
in the line.<br />