Section 2.1Technical <strong>Requirements</strong> For <strong>Service</strong> Up to and Including 5 kVRESIDENTIAL2152.1.6.4.4 Conduit and Secondary Wiring <strong>Requirements</strong>When the Consumer supplies the instrument transformer enclosure, the Consumer shall supply and install:• a continuous run of conduit (minimum 35 mm (1¼”) diameter) for the exclusive use of <strong>SaskPower</strong> between theinstrument transformer enclosure and the meter enclosure (to a maximum circuit length of 11 metres).• sealable LB fittings or similar conduit fittings, if required.• the bond on the meter socket when PVC conduit is used.<strong>SaskPower</strong> shall supply and install:• a continuous run of secondary conductors in the Consumer supplied conduit between the instrumenttransformers and the meter test switch (such that there are no splices or interruptions).• the test switch and the meter.Electric <strong>Service</strong> <strong>Requirements</strong> November, 2004