Section 2.2Technical <strong>Requirements</strong> For <strong>Service</strong> Up to and Including 5 kVFARM2272.2.5.2.4 Transformer-Rated Meter SocketsMeter sockets shall be:• configured and wired as per Figures 2-23 (5) & (7) and Figure 2-25 (1), (3) & (4), and installed as per Figure2-8.• complete with a ground connection.• within a circuit length of 11 metres from the instrument transformer enclosure. Exceptions require priorapproval from <strong>SaskPower</strong>, Metering <strong>Service</strong>s.• located outdoors.2.2.5.2.5 SpecificationsSingle Phase Buried <strong>Service</strong>• 400 A, 120/240 V Self-Contained Meter Socket (Figure 2-4)The enclosure shall:• have stud type line and neutral terminals so arranged as to permit straight in conductor connectionsand suitable for securing <strong>SaskPower</strong> compression lugs.• have minimum dimensions of 914 x 508 x 203 mm (36 x 20 x 8 inches).• be capable of using 78 mm (3 inch) conduit.The Consumer shall install the <strong>SaskPower</strong> supplied 3-wire current transformer. <strong>SaskPower</strong> shall make allterminations to the secondary of the current transformer.A single meter socket, rated up to 400 A, with dual wire connectors on the load side shall be permitted twosubdivisions. However, the subdivision of the consumer service can be accomplished within the dual lugmeter socket provided that the total ampere rating of the two consumer service disconnects does not exceed theampere rating of the meter socket.For supply service conductors exceeding 500 kcmil, or multiple conductors per phase, a splitter shall be used inconjunction with the meter socket. The splitter becomes <strong>SaskPower</strong>’s point of delivery.2.2.5.3 Instrument Transformers & Enclosures2.2.5.3.1 GeneralWhen the main service exceeds 200 A or 600 V, and the metering is not at <strong>SaskPower</strong>’s facilities, the instrumenttransformer enclosure shall be supplied and installed by the Consumer. For service voltage at 4160 V, the Consumershall supply and install the instrument transformer enclosure and meter socket.Revenue metering instrument transformers and other associated equipment supplied by <strong>SaskPower</strong> shall be usedexclusively for the purpose of <strong>SaskPower</strong> revenue metering.Electric <strong>Service</strong> <strong>Requirements</strong> November, 2004

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!