Section 2.2Technical <strong>Requirements</strong> For <strong>Service</strong> Up to and Including 5 kVFARM2232.2.4.1 Standard <strong>Service</strong>2.2.4.1.1 Single Phase <strong>Service</strong> up to 300 VFor supply services up to 200 A, options include:• <strong>SaskPower</strong> supplied Rural Metering (with or without a standby transfer switch) as per Figure 2-12, 2-13 or2-14.The Rural Metering consists of a meter socket, thermal circuit breaker and an integrated splitter compartment forConsumer service conductors not exceeding 350 kcmil.For supply services greater than 200 A, options include:• Consumer supplied 400 A, 120/240 V self-contained meter socket as per Figure 2-4 and Table 2-1.• Consumer supplied outside splitter as per Figure 2-7 and 2-8 and Table 2-1.• Consumer supplied service termination / CT enclosure as per Figure 2-4 (a) and Table 2-1.• Secondary terminals of <strong>SaskPower</strong> supplied pad-mounted transformer.2.2.4.1.2 Single Phase <strong>Service</strong> greater than 300 VFor supply services up to 200 A, options include:• Consumer supplied outside splitter, as per Figure 2-7 and 2-10 and Table 2-1.• <strong>SaskPower</strong> supplied F-Cabinet (240/480 V) as per Figure 2-15.• Secondary terminals of <strong>SaskPower</strong> supplied pad-mounted transformer.2.2.4.1.3 Polyphase <strong>Service</strong> up to 300 VFor supply services up to 200 A, options include:• Consumer supplied self-contained meter socket (limited to <strong>SaskPower</strong> supplied 4/0 cable), as per Figure 2-2and Table 2-1.• Consumer supplied outside splitter, where supply service conductors exceed 4/0 in size, as per Figure 2-7 inconjunction with Figure 2-2 and Table 2-1.• <strong>SaskPower</strong> supplied F-Cabinet, as per Figure 2-16.• secondary terminals of <strong>SaskPower</strong> supplied pad-mounted transformer.For supply services greater than 200 A, options include:• Consumer supplied outside splitter, as per Figure 2-7 and 2-8 and Table 2-1.• Consumer supplied service termination / CT enclosure as per Figure 2-4 (b) and Table 2-1.• secondary terminals of <strong>SaskPower</strong> supplied pad-mounted transformer.Electric <strong>Service</strong> <strong>Requirements</strong> November, 2004

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!